
22
FLEX I/O AC Digital Output Modules
Publication 1794-IN103D-EN-P - July 2018
Derating Curve for 1794-OA16
Mounting
Temperature, max.
Normal horizontal
55 °C
Other mounting positions (including inverted horizontal, vertical)
51 °C
0
72
10
20
30
40
50
55
60
V
in
On-state
V
oltage
(
V
AC)
Ambient Temperature
oC
The area within the curve represents the safe operating range for the module under
various conditions of user supplied 120
V
AC supply voltages and ambient temperatures.
= Other mounting positions (including inverted horizontal, vertical)
safe operating range
80
88
96
102
110
115
120
132
51
= Normal mounting safe operating range. Includes
130