Allen-Bradley 1794-IA8 Installation Manual Download Page 2

2

               

Publication 1794-IN102B-EN-P - June 2004

European Hazardous Location Approval

The following module is European Zone 2 approved: 1794-IA8K.

Installing Your ac Digital Input Module

The module mounts on a 1794 terminal base.

1.

Rotate the keyswitch (1) on the terminal base (2) clockwise to position 

8

 as required for this type of module. 

2.

Make certain the flexbus connector (3) is pushed all the way to the left 
to connect with the neighboring terminal base/adapter. 

You cannot 

install the module unless the connector is fully extended.

3.

Make sure the pins on the bottom of the module are straight so they 
will align properly with the connector in the terminal base.

4.

Position the module (4) with its alignment bar (5) aligned with the 
groove (6) on the terminal base.

5.

Press firmly and evenly to seat the module in the terminal base unit. 
The  module is seated when the latching mechanism (7) is locked into 
the module.

Connecting Wiring for the 1794-IA8 and -IA8K

1. For 1794-TB2, -TB3, or -TB3S - 

Connect individual input wiring to 

even numbered terminals on the 0-15 row (A) as indicated in the table 
below .

 

For 1794-TBN - 

Connect individual input wiring to numbered 

terminals on the 16-33 row (B) as indicated in the table below.

2. For 1794-TB2 - 

Connect the associated 120V ac power lead (L1) of 

the input device to the corresponding odd numbered terminals on the 
0-15 row A for each input as indicated in the table below. (The odd 
numbered terminals on row A are internally connected to 120V ac 
L1.)

For 1794-TB3, or -TB3S - 

Connect the associated 120V ac power 

lead (L1) of the input device to the corresponding odd numbered 
terminals on the 34-51 row (C) or to the corresponding terminal on 
row (C) for each input as indicated in the table below. (The odd 
numbered terminals on row (A) and the terminals of row (C) are 
internally connected to 120V ac power L1.)

 

 

For 1794-TBN - 

Connect the associated 120V ac power lead (L1) of 

the input device to the corresponding odd numbered terminal on the 
34-51 row (C) for each input as indicated in the table below. (The 
120V ac power terminals of row (C) are internally connected 
together.)

3.

Connect 120V ac power (L1) to terminal 34 on the 34-51 row (C).

4.

Connect 120V ac common (L2) to terminal 16 on the 16-33 row (B).

5.

If daisychaining power to the next terminal base, connect a jumper 
from terminal 51 (+120V ac L1) on this base unit to terminal 34 on 
the next base unit

6.

.If continuing ac common to the next base unit, connect a jumper 
from terminal 33 (120V common L2) on this base unit to terminal 16 
on the next base unit.

Wiring Connections for the 1794-IA8 and -IA8K

European Zone 2 Certification (The following applies when the product bears 
the EEx Marking)

This equipment is intended for use in potentially explosive atmospheres as defined by 
European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this 
equipment has been found to comply with the Essential Health and Safety 
Requirements relating to the design and construction of Category 3 equipment 
intended for use in potentially explosive atmospheres, given in Annex II to this 
Directive.  The examination and test results are recorded in confidential report No. 28 
682 010.
Compliance with the Essential Health and Safety Requirements has been assured by 
compliance with EN 50021.

IMPORTANT

Observe the following additional Zone 2 certification requirements.

This equipment is not resistant to sunlight or other sources of UV 
radiation.

The secondary of a current transformer shall not be open-circuited 
when applied in Class I, Zone 2 environments.

Equipment of lesser Enclosure Type Rating must be installed in an 
enclosure providing at least IP54 protection when applied in Class I, 
Zone 2 environments.

This equipment shall be used within its specified ratings defined by 
Allen-Bradley.

Provision shall be made to prevent the rated voltage from being 
exceeded by transient disturbances of more than 40% when 
applied in Class I, Zone 2 environments

ATTENTION

During mounting of all devices, be sure that all debris 
(metal chips, wire strands, etc.) is kept from falling 
into the module. Debris that falls into the module 
could cause damage on power up.

WARNING

If you remove or insert the module while the backplane 
power is on, an electrical arc can occur. This could cause an 
explosion in hazardous location installations. Be sure that 
power is removed or the area is nonhazardous before 
proceeding..

1

2

3

4

5

6

7

Input

1794-TB2,-TB3, -TB3S

1794-TBN

Input 
Terminal

120V ac 
Supply

Input 
Terminal

120V ac 
Supply

Input 0

A-0

A-1

1

/C-35

B-0

C-1

2

Input 1

A-2

A-3

1

/C-36

B-2

C-3

2

Input 2

A-4

A-5

1

/C-37

B-4

C-5

2

Input 3

A-6

A-7

1

/C-38

B-6

C-7

2

Input 4

A-8

A-9

1

/C-39

B-8

C-9

2

Input 5

A-10

A-11

1

/C-40

B-10

C-11

2

Input 6

A-12

A-13

1

/C-41

B-12

C-13

2

Input 7

A-14

A-15

1

/C-42

B-14

C-15

2

A = Input terminals (Even numbered terminals 

 

0 thru 14)

 

B = Common terminals

 

C = Power terminals (C-34 and C-51 on -TB2; C-34

 

 thru C-51 on -TB3 and -TB3S)

B = Even numbered Input terminals 
0-14, ac common terminals 16 and 33

 

C = Power terminals C-34 and C-51, and 
odd numbered input terminals 1 thru 15

1 A-1, 3, 5, 7, 9, 11, 13 and 15 on the 1794-TB2, -TB3 and -TB3S are internally connected in the

 

 module to 120V ac L1.

 

2 C-1, 3, 5, 7, 9, 11, 13 and 15 on the 1794-TBN are internally connected in the module to 

 

120V ac L1.

Reviews: