Addressing Reference
1785 PLC-5
5
Figure 3
Logical Addressing for I/O Image Tables
File Type
O = Output
I = Input
I/O Rack Number
0 – 3 octal for PLC-5/10, -5/11 -5/12, -5/15,
-5/20
0 – 7 octal for PLC-5/25, -5/30
0 – 17 octal for PLC-5/40, -5/40L
0 – 27 octal for PLC-5/60, -5/60L, -5/80
Bit Number
0 – 17 Octal
I/O Group Number
0 – 7 Octal
Logical Address Identifier
File Separator
Bit Separator (if addressing a bit)
$ I : 12 3 / 12
17399–I
Word
No.
Figure 4
Word of Input or Output Image File
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
PLC Data Type: signed word (negative values in 2’s complement form)
Range: –32,768 thru +32,767
17400–I
Logical Addressing for I/O
Image Tables