Allen-Bradley 177R-M4AXP Installation Instructions Manual Download Page 7

Industrial Non-display Computers     

7

Rockwell Automation Publication 6177R-IN001G-EN-P - July 2013

Installation Guidelines

Follow these guidelines to make sure your product provides safe and reliable service:

The installation site must have sufficient power.

The enclosure must have sufficient space around air inlets and outlets to provide the 
circulation necessary for cooling. Never allow air passages to become obstructed.

The ambient air temperature must not exceed the maximum operating temperature. 
Consider heat produced by other devices in the enclosure. You may need a user-supplied 
fan, heat exchanger, or air conditioner to meet this condition.

The humidity of the ambient air must not exceed specified limits and must avoid 
condensation. 

In dry environments, static charges build up easily. Proper grounding of the equipment 
through the AC power cord helps to reduce static discharges, which may cause shocks 
and damage electronic components.

The enclosure or cover must remain in place at all times during operation. The cover 
provides protection against high voltages inside the product and inhibits 
radio-frequency emissions that might interfere with other equipment.

ATTENTION: 

To maintain an electrically safe installation, the AC powered products must be 

plugged into a grounded outlet.

TIP

Hot air rises. The temperature at the top of the enclosure is often higher than the temperature 
in other parts of the enclosure, especially if air is not circulating.

IMPORTANT

The product can operate at a range of extremes. However, the life span of any electronic device 
is shortened if you continuously operate the product at its highest, rated temperature.

Summary of Contents for 177R-M4AXP

Page 1: ...computer 6177R M4xxxxx rack mount the 1450R computer 6177R R4xxxxx It also describes how to make peripheral power and network connections Topic Page Important User Information 2 Additional Resources...

Page 2: ...ular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with res...

Page 3: ...y computers and specifications Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 ProvidesgeneralguidelinesforinstallingaRockwellAutomationindustrial system Product Certificati...

Page 4: ...nments due to conducted as well as radiated disturbance This equipment is supplied as open type equipment UL recognized equipment must be mounted within an enclosure that is suitably designed for thos...

Page 5: ...drive containing the original factory image You can use the supplied Computer System Cloning CD to restore the operating system from the recovery partition and create a new recovery image Refer to th...

Page 6: ...re Rack handles for the 1450R computer Mounting brackets for the 750R computer Mounting brackets for the 650R computer Mounting fasteners Installation instructions Quick start guidelines System CDs Ac...

Page 7: ...id condensation In dry environments static charges build up easily Proper grounding of the equipment through the AC power cord helps to reduce static discharges which may cause shocks and damage elect...

Page 8: ...ble connections Sufficient air flow throughout the system unit is required to maintain proper cooling Clearance should be enough to allow convenient installation or removal of peripheral components su...

Page 9: ...P July2013 ProductDimensions Review the product dimensions to estimate the clearance necessary for computer installation Dimensions are give in mm in 650R Computers catalog number 6177R M3 750R Comput...

Page 10: ...to the panel by using the four screw slots in the front plate Use M5 or 10 screws or larger Screws are not included ATTENTION Remove all electricalpower from the panel before making the cutout Make su...

Page 11: ...IN001G EN P July2013 Bottom Mounting Dimensions 650R Side Mounting Dimensions 650R Mounting Bracket Dimensions bottom side Dimensions are in mm in 243 9 6 232 6 9 16 232 6 9 16 Mounting Bracket Dimen...

Page 12: ...uter by using six screws There are two location options the computer s bottom side for an upright installation or the side cover for a wall installation 2 Drill four holes in the shelf or wall that co...

Page 13: ...rance for cables and air flow A rack cabinet with a depth of 610 mm 24 in is sufficient The computer must be supported by rack slides or fastened to a shelf The four flanges of the computer are intend...

Page 14: ...net 6 Insert the computer in the rack cabinet from the front of the cabinet 7 Fasten one rack mount flange to each side of the chassis with the slotted screws provided 8 Horizontally secure the comput...

Page 15: ...n an industrial or control room environment which uses some form of power isolation from the public low voltage mains ATTENTION Connect the AC power cable to a power source with an earth ground to pre...

Page 16: ...wer supply is internally protected against reverse polarity 1 Secure the DC power wires to the terminal block screws 2 Secure the ground wire to the GND terminal block screw 3 Apply 24V DC power to th...

Page 17: ...wered on If the computer does not display the correct time and date replace the battery IMPORTANT To prevent performance degradation of Ethernet communication do not subject the computer or cables to...

Page 18: ...hat prevent access to the RTC battery socket 5 Remove the battery a Insert a small screwdriver between the battery and spring latch to dislodge the battery from its socket ATTENTION A risk of fire and...

Page 19: ...ards peripherals board covers and system cables that have previously been removed d Reinstall the side cover e Connect all external cables and the AC power cord to the computer f Press the power switc...

Page 20: ...tility 3 Press F9 to load the default values 4 Press F10 to save the changes you made and close the Setup Utility TransporttheProduct If you need to ship the product via common carrier or otherwise tr...

Page 21: ...dissipation DC 650R 144 W Mechanical Dimensions HxWxD approx 650R 750R 1450R 274 x 427 x 215 mm 10 79 x 16 81 x 8 46 in 360 x 170 x 381 mm 14 17 x 6 69 x 15 01 in 176 x 431 x 465 mm 6 93 x 16 97 x 18...

Page 22: ...ns of conformity certificates and other certification details 6177R M4 6177R R4 6177R M3 c UL us UL c UL Listed per UL 60950 1 and CSA C22 2 No 60950 1 03 CE Marked for all applicable directives EMC 2...

Page 23: ...Industrial Non display Computers 23 Rockwell Automation Publication 6177R IN001G EN P July2013 Notes...

Page 24: ...o contact a special Customer Support number for initial help in getting your product up and running NewProductSatisfactionReturn Rockwell Automation tests all of its products to help ensure that they...

Reviews: