AC (120V) Output Module
(Cat. No. 1771-ODD)

Installation Instructions

 2

The 1771-ODD module is designed for a 10mA minimum current on each
output circuit. The total continuous current the module supports is 8A (2A
maximum per channel).  If this rating is exceeded, the module overheats
and damage may occur.

Suppression

Surge suppression circuitry is provided for the output triacs in this module.
To suppress high-voltage transients from the ac line, a metal-oxide varistor
(MOV) is provided between each set of terminals on the module.  In each
output circuit an RC network limits the magnitude of voltage transients
that may occur when a device is wired in parallel or series with hard
contacts.

Loads with inductive characteristics may require additional suppression
devices.  The impedance characteristic of the load is the most important
factor in selecting a suppression device; thus no single suppression device
can be recommended for every possible load.  See Table 1 for acceptable
suppression devices for typical loads.

Table 1
AllenBradley Suppressors

AllenBradley Equipment

Suppressor Catalog Number

Motor Starter Bulletin 509

599K04

1

Motor Starter Bulletin 709

1401N10

1

Relay Bulletin 700 Type N or P

700N5/700N9

Miscellaneous

700N24

2

For starters with 120V AC coils

Bulletin 700N24 is a universal surge suppressor. You can use it on electromagnetic devices with the limitation of

35 sealed VA, 150V.

The isolated output module is powered by the power supply connected to
the I/O chassis backplane.  The module requires a maximum current of
420mA from the +5V dc output of this supply.  Total the current
requirements of this module with the other modules in the I/O chassis to
avoid overloading the supply or the I/O chassis backplane.

Power Supply Requirements