Installation
Chapter 3
35
3.
Set the control’s baud rate of 9600 baud. The baud rate can be
changed by altering the bits of PAL table 161, index 0. Change bits
2,1,0 to a value of 1,1,0. Do not alter the other bits in index 0 as they
control the communications between the control and its peripheral
devices. if the executive tape being used does not have PAL edit
capabilities, you will not be able to change or set the control baud
rate. If you do not have this capability, contact the OEM and request
the change.
Use the following procedure to convert the recorder for 230V AC
operation:
WARNING: Power must be moved from the recorder before
converting for 230V AC operation. Performing the conversion
with power applied to the recorder may cause serious injury to
personnel.
1.
Remove the power cord from the recorder and the grounded AC
outlet.
2.
Remove the four screws which attach the front panel to the case
(Figure 3.5).
3.
Disconnect the ground wire from the bottom of the front panel.
Figure 3.5
Converting to 230V Operation
POWER
STOP REWIND
BOTH
END OF
TRACKS USED TRACK
IN ERROR OUT
DATA
WRITE
INHB
RECORD
ON
TAPE
READ
FROM
TAPE
ON
OFF
DATA CARTRIDGE RECORDER
TRACK
SELECT
BAUD
RATE
1
2
CONT
300
600
1200
2400
4800
9600
CONTROLLER
EQUIPMENT
115V 5060 HZ
3 AMP
5A SB
3 AG
11294
BULLETIN 1770
230 VAC 1/4A SB
50/60 HZ 3AG
When using unit for 230 volt operation,
use the above label.
Screw
Screw
Screw
Screw
Converting for 230 V AC
Operation