Allen-Bradley 1769-PB2 Product Information Download Page 2

2

    Compact Power Supply

Rockwell Automation Publication 1769-PC013A-EN-P - August 2014

Environment and Enclosure

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations 
and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the 
hazardous location temperature code. When combining products within a system, the most adverse temperature code 
(lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of 
equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation.

Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 
2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque 
d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont 
combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être 
utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont 
sujettes à inspection par les autorités locales qualifiées au moment de l'installation

European Hazardous Location Approval

The following applies to products marked 

 II 3 G: This equipment:

• is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been 

found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 
equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive. Compliance 
with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0. 
See the EC Declaration of Conformity at 

http://www.rockwellautomation.com/products/certification

 for details. The type 

of protection used is “Ex nA IIC T4- Gc“, according to EN 60079-15. The specific temperature code is marked on the 
product.

• is intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air mixtures are unlikely to 

occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification 
according to ATEX directive 1999/92/EC.

• complies with standards EN 60079-0:2009 and EN 60079-15:2010, reference certificate number ITS09ATEX46118X.

ATTENTION: 

• Before installing, configuring, operating, or maintaining this product, read this document and the 

documents listed in the Additional Resources section for installing, configuring, or operating equipment. 
Users should familiarize themselves with installation and wiring instructions in addition to requirements 
of all applicable codes, laws, and standards.

• Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be 

carried out by suitably trained personnel in accordance with applicable code of practice. In case of 
malfunction or damage, no attempts at repair should be made. The module should be returned to the 
manufacturer for repair. Do not dismantle the module.

• If this equipment is used in a manner not specified by the manufacturer, the protection provided by the 

equipment may be impaired.

• For Compact Power Supplies, this equipment is certified for use only within the surrounding air 

temperature range of 0…60 °C (32…140 °F). The equipment must not be used outside of this range.

• Solid-state equipment has operational characteristics differing from those of electromechanical 

equipment. Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Controls, 
publication SGI-1.1, available from your local Rockwell Automation sales office or online at 

http://www.rockwellautomation.com/literature

, describes some important differences between 

solid-state equipment and hard-wired electromechanical devices.

IMPORTANT

Any illustrations, charts, sample programs, and layout examples shown in this publication are 
intended solely for the purposes of example. Since there are many variables and requirements 
associated with any particular installation, Rockwell Automation does not assume responsibility or 
liability for actual use based upon the examples shown in this publication.

ATTENTION: 

This equipment is intended for use in a Pollution Degree 2 industrial environment, in 

overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without 
derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without 
appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and 
other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is 
suitably designed for those specific environmental conditions that will be present and appropriately 
designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have 
suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame 
spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be 
accessible only by the use of a tool. Subsequent sections of this publication may contain additional 
information regarding specific enclosure type ratings that are required to comply with certain product safety 
certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 

1770-4.1 

for additional installation 

requirements

• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by 

different types of enclosure

WARNING: 

EXPLOSION HAZARD

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous. 
• Do not disconnect connections to this equipment unless power has been removed or the area is known to 

be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding 
latches, threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must be changed only in an area known to be nonhazardous.

AVERTISSEMENT: 

RISQUE D'EXPLOSION

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher 

l'équipement.

• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les 

connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets 
coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement 

de Classe I, Division 2.

• S'assurer que l'environnement est classé non dangereux avant de changer les piles.

WARNING: 

Special Conditions for Safe Use:

• This equipment shall be mounted in an ATEX-certified enclosure with a minimum ingress protection 

rating of IP54 (as defined in IEC60529) and used in an environment of not more than Pollution Degree 2 
(as defined in IEC 60664-1) when applied in Zone 2 environments. The enclosure must have a 
tool-removable cover or door.

• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of 

more than 140% of the rated voltage when applied in Zone 2 environments.

• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded 

connectors, or other means provided with this product.

• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.