Publication 1763-RM001C-EN-P - October 2009
Recipe and Data Logging
435
Number of Records
Using Queue 0 as an example, each record consumes:
In this example, each record consumes 18 bytes. So if one queue was
configured, the maximum number of records that could be stored would
be 7281. The maximum number of records is calculated by:
Maximum Number of Records = Data Log File Size/Record Size
= 128K bytes/18 bytes
= (128)(1024)/18
= 7281 records
Example Queue 5
String Length of Record
The size of a record is limited so that the length of the maximum
formatted string does not exceed 80 characters. The following table can
be used to determine the formatted string length.
Record Field
Memory Consumption
Date
2 bytes
Time
2 bytes
N7:11
2 bytes
L14:0
4 bytes
T4:5.ACC
2 bytes
I1:3.0
2 bytes
B3:2
2 bytes
Integrity Check
2 bytes
Total
18 bytes
Queue 5 (Time =
✔
, Delimiter = TAB)
Time
N7:11
I1:3.0
I1:2.1
Record 0
20:00:00
TAB
2315
TAB
8190
TAB
4465
Record 1
20:30:00
TAB
2400
TAB
8210
TAB
4375
Record 2
21:00:00
TAB
2275
TAB
8150
TAB
4335
Record 3
21:30:00
TAB
2380
TAB
8195
TAB
4360
Record 4
22:00:00
TAB
2293
TAB
8390
TAB
4375
Record 5
22:30:00
TAB
2301
TAB
8400
TAB
4405
Record 6
23:00:00
TAB
2308
TAB
8100
TAB
4395