Rockwell Automation Publication 1757-UM012A-EN-P - July 2011
149
Troubleshoot the Linking Device
Appendix A
Reset the Linking Device
To manually use the reset jumper or reset button, use the
illustration and procedures in this section.
To use the Web page to perform a remote reset, see
.
You can reset the linking device by using one of these three ways:
•
Reset jumper (locally)
•
Reset button (locally)
•
Reset Web page (remotely)
You can reset the linking device to the following defaults:
•
Reset Configuration
•
Reset to Factory Defaults
Reset Configuration
The Reset Configuration removes power from the linking device’s battery,
deleting all downloaded fieldbus configurations. The linking device retains its
network configuration and Web page password information through this reset.
Follow these steps to perform a reset configuration.
1.
Remove power from the linking device.
IMPORTANT
When you reset the linking device, it no longer communicates with the
fieldbus devices. Make sure your process is shut down or under manual
control before you reset the linking device.
WARNING:
If you insert or remove the jumper while the power is
on, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Summary of Contents for 1757-FFLD2
Page 8: ...8 Rockwell Automation Publication 1757 UM012A EN P July 2011 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 1757 UM012A EN P July 2011 Preface Notes...
Page 178: ...178 Rockwell Automation Publication 1757 UM012A EN P July 2011 Glossary Notes...
Page 182: ...182 Rockwell Automation Publication 1757 UM012A EN P July 2011 Index Notes...
Page 183: ......