Chapter 7
Linking Device Function Blocks
Resource Function Block Options
describes the options with the resource block.
29
SET_FSTATE
Unsigned8
1: Off
2: Set
1
E
AUTO
Allows the fault state condition to be manually
initiated by selecting Set.
30
CLR_FSTATE
Unsigned8
1: Off
2: Clear
1
E
AUTO
Writing a Clear to this parameter will clear the device
fault state if the field condition, if any, has cleared.
31
MAX_NOTIFY
Unsigned8
Set by mfgr
3
None
RO
Not user configurable.
32
LIM_NOTIFY
Unsigned8
0 to MAX_
NOTIFY
MAX_
NOTIFY
None
RO
Not user configurable.
33
CONFIRM_TIME
Unsigned32
640000
1/32 ms
AUTO
Not user configurable.
34
WRITE_LOCK
Unsigned8
1:Not Locked
2:Locked
1
E
AUTO
If set, no writes from anywhere are allowed, except to
clear WRITE_LOCK. Block inputs will continue to be
updated.
35
UPDATE_EVT
DS-73
N/A
RO
This alert is generated by any change to the static data.
36
BLOCK_ALM
DS-72
N/A
RO
The block alarm is used for all configuration, hardware,
connection failure or system anomalies in the block.
The cause of the alert is entered in the subcode field.
The first alert to become active will set the Active
status in the Status attribute. As soon as the
Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing
the Active status, if the subcode has changed.
37
ALARM_SUM
DS-74
See
ALARM_SUM
and
ACK_OPTION
Bits on page 110
N/A
RO
The current alert status, unacknowledged states,
unreported states, and disabled states of the alarms
associated with the function block.
38
ACK_OPTION
Bitstring(2)
0: Auto ACK
Disable
1: Auto ACK
Enable
0
N/A
AUTO
Selection of whether alarms associated with the block
will be automatically acknowledged. See
ALARM_SUM and ACK_OPTION on
.
39
WRITE_PRI
Unsigned8
0 to 15
0
None
AUTO
Priority of the alarm generated by clearing the write
lock.
40
WRITE_ALM
DS-72
None
RO
This alert is generated if the write lock parameter is
cleared.
41
ITK_VER
Unsigned16
N/A
RO
This parameter specifies to which ITK version the
device is certified (only for certified devices).
Table 5 - RES Block Parameters
Index
Parameter
Data Type
(length)
Valid Range/
Options
Default
Value
Units
Edit
Mode
Description
Table 6 - Block Options
Bit
Meaning
ALARM_SUM and ACK_OPTION Bits
0
Writes have been enabled
1–6
Reserved
7
Block alarm
Summary of Contents for 1757-FFLD2
Page 8: ...8 Rockwell Automation Publication 1757 UM012A EN P July 2011 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 1757 UM012A EN P July 2011 Preface Notes...
Page 178: ...178 Rockwell Automation Publication 1757 UM012A EN P July 2011 Glossary Notes...
Page 182: ...182 Rockwell Automation Publication 1757 UM012A EN P July 2011 Index Notes...
Page 183: ......