
Rockwell Automation Publication 1756-RM001I-EN-P - May 2012
87
Chapter
8
Faults in the ControlLogix System
In addition to providing information on module fault reporting, this chapter
explains two example conditions that will generate a fault in a SIL 2-certified
ControlLogix system:
•
Keyswitch changing out of Run mode
•
High alarm condition on an analog input module
Detecting and Reacting to
Faults
The ControlLogix architecture provides many ways of detecting and reacting to
faults in the system.
•
Various device objects can be interrogated to determine the current
operating status.
•
Modules provide run-time status of their operation and of the process that
is executing.
•
You can configure a ControlLogix system to identify and handle faults,
including such tasks as:
–
developing a fault routine.
–
creating a user-defined major fault.
–
monitoring minor faults.
–
developing a power-up routine.
See the Logix5000 Controllers Common Procedures Programming
Manual, publication
, for more information.
It is your responsibility to determine what data is most appropriate for your
application to initiate a shutdown sequence.
Topic
Page
Detecting and Reacting to Faults
Module Fault Reporting for Any ControlLogix or FLEX I/O Module
Checking Keyswitch Position with GSV Instruction
Examining an 1756 Analog Input Module’s High Alarm
TIP
To help handle faults, make sure you have completed the input (see
Summary of Contents for 1756-L6 Series
Page 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Page 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Page 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Page 133: ...Allen Bradley Motors ...