PFD Calculations for a SIL 2 System
2-Year PFD Calculations
The PFD calculations in
are calculated for a 2-year proof test interval
and are specific to ControlLogix system components.
Table 11 - PFD Calculations - 2-year for ControlLogix Component
Cat. No.
(1)
(2)
Description
61508
(2010)
Mean Time Between
Failure (MTBF)
(9)
λ
(10)
Calculated PFD
1oo1
Architecture
1oo2
Architecture
1756-A
XX
/B
(3)
ControlLogix chassis
22,652,009.8
4.415E-08
1.9358E-05
—
1756-A4LXT
ControlLogix-XT chassis
1,069,120
9.353E-07
4.1015E-04
—
1756-A5XT/B
ControlLogix-XT chassis
734,420
1.362E-06
5.9707E-04
—
1756-A7LXT
ControlLogix-XT chassis
27,628,178
3.619E-08
1.5871E-05
—
1756-A7XT/B
ControlLogix-XT chassis
1,081,600
9.246E-07
4.0542E-04
—
1756-PB72/C
ControlLogix DC power supply
31,561,095
3.168E-08
1.3894E-05
—
1756-PA72/C
ControlLogix AC power supply
18,336,146
5.454E-08
2.3915E-05
—
1756-PA75/B
ControlLogix AC power supply
18,693,044
5.350E-08
2.3458E-05
—
1756-PA75R
ControlLogix AC redundant power supply
(8)
1,412,877
7.078E-07
3.1036E-04
—
1756-PB75/B
ControlLogix DC power supply
15,675,475
6.379E-08
2.7974-05
—
1756-PB75R
ControlLogix DC redundant power supply
1,736,020
5.760E-07
2.5259E-04
—
1756-PAXT/B
ControlLogix-XT AC power supply
18,693,044
5.350E-08
4.0122E-08
—
1756-PBXT/B
ControlLogix-XT DC power supply
1,855,360
5.390E-07
2.634E-04
—
1756-PC75/B
(4)
ControlLogix DC power supply
5,894,836
1.696E-07
7.4387E-05
—
1756-PH75/B
ControlLogix DC power supply
2,119,520
4.718E-07
2.0689E-04
—
1756-PSCA
(4)
ControlLogix redundant power supply adapter
45,146,727
2.215E-08
9.7128E-06
—
1756-PSCA2
ControlLogix redundant power supply adapter
38,461,280
2.600e-08
1.1401E-05
—
1786-RPFS
ControlNet fiber repeater - short
26,461,760
3.779E-08
1.6571E-05
—
1786-RPFM
ControlNet fiber repeater - medium
16,697,862
5.989E-08
2.6261E-05
—
1786-RPFL
ControlNet fiber repeater - long
5717227
1.749E-07
7.6698E-05
—
1786-RPCD
ControlNet hub repeater
28,654,080
3.490E-08
1.5303-05
—
1756-L61/B
ControlLogix 2 MB controller
1,000,053
9.999E-07
4.3848E-04
—
1756-L62/B
ControlLogix 4 MB controller
1,034,830
9.663E-07
4.2374E-04
—
1756-L63/B
ControlLogix 8 MB controller
1,055,910
9.471E-07
4.1528E-04
—
1756-L63XT/B
ControlLogix-XT controller
357,760
2.795E-06
1.2257E-03
—
1756-L71/B
(5)
ControlLogix 2 MB controller
x
9,946,827
1.005E-07
8.9E-04
—
1756-L72/B
ControlLogix 4 MB controller
x
9,946,827
1.005E-07
8.9E-04
—
1756-L73/B
ControlLogix 8 MB controller
x
9,946,827
1.005E-07
8.9E-04
—
1756-L73XT/B
ControlLogix-XT 8 MB controller
x
9,946,827
1.005E-07
8.9E-04
—
1756-L74/B
ControlLogix 16 MB controller
x
9,946,827
1.005E-07
8.9E-04
—
1756-L75/B
ControlLogix 32 MB controller
x
9,946,827
1.005E-07
8.9E-04
—
1756-CNB/E
ControlLogix ControlNet communication module
1,786,977
5.596E-07
2.04539E-04
—
1756-CNBR/E
ControlLogix redundant ControlNet communication
module
2,608,543
3.834E-07
1.6810E-04
—
1756-CN2/B
(6)
ControlLogix ControlNet communication module
x
1,096,299
9.122E-07
3.9998E-04
—
1756-CN2R/B
ControlLogix redundant ControlNet communication
module
x
1,096,299
9.122E-07
3.9998E-04
—
Summary of Contents for 1756-L6 Series
Page 24: ...24 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 1 SIL Policy Notes ...
Page 76: ...76 Rockwell Automation Publication 1756 RM001I EN P May 2012 Chapter 6 FLEX I O Modules Notes ...
Page 126: ...126 Rockwell Automation Publication 1756 RM001I EN P May 2012 Appendix D Checklists Notes ...
Page 133: ...Allen Bradley Motors ...