Publication 1764-UM001A-US-P
Installing and Wiring Your Module
3-5
Figure 3.5 JW4 Pin Assignments and Settings
Use the worksheet in appendix B to document the selected jumper setting of
jumper JW4. Documenting your selection provides others with information
necessary to integrate the module with their SLC 500 fixed or modular controllers.
3 5
1
4 6
2
SLC 500
BASIC MODULE
CA
T
S
ER
SERIAL
NO.
FRN
JW1
1
2
3
4
5
6
7
8
9
U
L
PRT1
1
2
3
4
5
6
7
8
9
PRT2
SA
JW2
DH485
PRT1 Port = Program port with
default
communication settings
PRT2 Port = ASCII interface port
DH485 Port = Run-time DH485 only
Pin Assignments
PRT1 Port = ASCII interface port
PRT2 Port = ASCII interface port
DH485 Port = Program port with DH485 protocol
(shipped configuration)
PRT1 Port = Program port with programmed communication settings
PRT2 Port = ASCII interface port
DH485 Port = Run-time DH485 only
PRT1 Port = Program port with programmed communication settings
PRT2 Port = DF1 protocol
DH485 Port = Disabled
IMPORTANT
The first setting shown above is the default configuration. When
the jumper is set in this position, the module always powers up in
Command mode
at 1200 baud, no parity, 8 data bits, and 1 stop
bit.
ATTENTION
All other jumper settings for JW4 are illegal and may cause
damage to the module.
IMPORTANT
•
When DF1 protocol is selected for port PRT2, port DH485 is
not available for DH485 programming or run-time operation.
•
DF1 communication must be enabled through the BASIC
program.
Summary of Contents for 1746-BAS
Page 4: ...Publication 1746 UM004A US P Summary of Changes ii...
Page 8: ...Publication 1746 UM004A US P Table of Contents iv...
Page 26: ...Publication 1746 UM004A US P 1 14 Module and Development Software Overview...
Page 34: ...Publication 1764 UM001A US P 2 8 Component Selection...
Page 70: ...Publication 176 UM04A US P A 4 Specifications...
Page 83: ...Spare Allen Bradley Parts...