ArmorPOINT RTD and Thermocouple Input Modules
15
Publication 1738-IN005B-EN-E - January 2013
Vibration
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
Emissions CSPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM @ 30 MHz…1000 MHz
10V/m with 200 Hz 50% pulse 100% AM @ 900 Mhz
EFT/B immunity
IEC 61000-4-4:
±3 kV @ 5 kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on shielded ports
Conducted RF immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80% AM @ 150 kHz…80 MHz
Certifications
Certification (when
product is marked)
(1)
Value
c-UL-us
UL-listed Industrial Control Equipment, certified for US and Canada
CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
See the Product Certification link at
http://www.ab.com
for Declaration of Conformity, Certificates, and other
certification details.
Environmental Specifications
Attribute
Value