Publication 1734-UM002C-EN-P - July 2003
6-2
Troubleshooting the 1734-ADN(X) Adapter
Use the table below to troubleshoot your adapter.
Indicator:
Indication:
Probable Cause:
Take This Action:
System Power
Off
Any of the following:
1. Not active
2. Field power is OFF
3. DC-DC converter
problem
1. Check adapter
configuration
2. Turn field power ON
3. Check DC-DC
converter
Green
Any of the following:
1. System power ON
2. DC-DC converter
active (5V)
None
Field Power
Off
Any of the following:
1. Not active
2. Field power is OFF
1. Check adapter
configuration
2. Turn field power ON
Green
Power ON, 24V present
None
Adapter Status
Off
No power applied to device Power the adapter
Green
Device operating normally
None
Flashing Green
Device needs to be
commissioned because
configuration is missing,
incomplete or incorrect
Check configuration and
recommission the adapter
Flashing Red
Recoverable fault
Make sure the adapter
does not need a FLASH
update
Red
Unrecoverable fault may
require device replacement
Replace the adapter
Flashing
Red/Green
Device is in self-test
Wait for self-test to finish
Summary of Contents for 1734-ADNX
Page 1: ...POINT I O DeviceNet Adapter 1734 ADN 1734 ADNX User Manual...
Page 4: ...Publication 1734 UM002C EN P July 2003 Summary of Changes 2 Notes...
Page 14: ...Publication 1734 UM002C EN P July 2003 Table of Contents iv...
Page 80: ...Publication 1734 UM002C EN P July 2003 A 4 Specifications Notes...
Page 112: ...Publication 1734 UM002C EN P July 2003 B 32 1734 ADNX Quick Start Notes...
Page 128: ...Publication 1734 UM002C EN P July 2003 D 14 Default Data Maps...
Page 135: ......