Allen-Bradley 1606-XLE480FP Installation Instructions Download Page 2

 

Rockwell Automation Support 

For Technical Support, visit ROK.AUTO/SUPPORT. 

The information in this document is believed to be accurate and reliable and may change without notice.

 

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec. 

Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. 

www.rockwellautomation.com 

Power, Control and Information Solution Headquarters 

Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax. (1) 414.382.4444 
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgien, Tel: (32) 2663.0600, Fax (32) 2663.0640 
Asia Pacific: Rockwell Automation,Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887.4778, Fax (852) 2508.1846 
Turkey: Rockwell Otomasyon Ticraet A.

Ş

., Kar Plaza 

İş

 Merkezi E Blok Kat:6 34752 

İ

çerenköy, Istanbul, Tel: (90) 216.5698400  (EEE Yönetmeli

ğ

ine Uygundur) 

 

Publication 1606-IN055A-EN-E - June 2020

 

DIR 10005140927 (Version 01)

Copyright © 2020 Rockwell Automation, Inc. All Rights Reserved..

 

 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in output current and over 

voltage category is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase 

the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%, 

the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without additional protection 

device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or C-Characteristic to avoid a nuisance 

tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or 

surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2) 

environments. 
Classification: ATEX: EPS 17 ATEX 1 089 X, II 3G EX ec nC IIC T4 Gc / IECEx EPS 19.0103X 

WARNING EXPLOSION HAZARDS! 

Do not use with DC input voltages. 
Do not use with AC input voltages below 90Vac. 
Use only in standard vertical mounting orientation with the input terminals on bottom of the unit. 
Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is known to 

be non-hazardous. 
The equipment shall be installed in an enclosure that provides a degree of protection not less than IP54 in accordance with 

EN 60079-7 or EN 60079-15. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any kind of loads, including 

unlimited inductive and capacitive loads. If capacitors with a capacitance >0.25F are connected, the unit might charge the 

capacitor in an intermittent mode. 
Do not apply return voltages from the load to the output higher than 63V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC-OK LED reports an output voltage above 90% of the adjusted voltage of a running device. 
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on. Contact ratings: 60Vdc 

0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output shuts down and starts 

automatically again after cooling off. 
At heavy overloads (when output voltage falls below 26V), the device delivers continuous output current for 2s. After this, the 

output is switched off for 18s before a new start attempt is automatically performed. This cycle is repeated as long as the 

overload exists. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to exceed 60°C. The output 

voltage of all devices shall be adjusted to the same value (±100mV) in “Single Use” mode with the same load conditions on 

all units, or the units can be left with the factory settings. After the adjustments, set the unit to “Parallel Use” mode, in order to 

achieve load sharing. The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is 

approx. 4% higher than at nominal load. Energize all units at the same time. It also might be necessary to cycle the input 

power (turn-off for at least five seconds), if the output was in overload or short circuit. If more than three devices are 

connected in parallel, a diode, fuse or circuit breaker with a rating of 16A or 20A is required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many devices in series as 

needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 60V. The output shuts down and 

performs three restart attempts. If the failure continues, the output shuts down. Cycle input power to reset. 
 

 

Functional Diagram 

+

+

-

-

Output

Over-

Voltage

Protection

PFC

Converter

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter

L

N

-

13
14

Output

Voltage

Regulator

Output

Voltage

Monitor

V

OUT

DC-ok

Contact

DC-ok

LED

DC-ok

Relay

Link for

Parallel

Use

 
 

Output Characteristic 

Output voltage

 (single use)

17.5A

48V

Output current

24V

0V

2.5A

7.5A

10A

12.5A

0A

Adjustment range

56V

5A

A: continuous current

B: intermitted current

15A

A

B

 
 

Temperature Range 

Allowed output current at 48V

Ambient temperature

0A

-25

A: continuous

B: short term (max. 5s)

12A

+25

0

+45

+70°C

7.5A

A

B

10A

+60

 
 

 