Output

The output provides a SELV/PELV rated voltage, which is galvanically isolated 
from the input voltage.

The output is designed to supply any kind of loads, including capacitive and 
inductive loads. If capacitors with a capacitance > 3 F are connected to the 
output, the unit might charge the capacitor in an intermittent mode. Example 
capacitors with a capacitance > 3 F may include electric double layer capacitors 
(EDLCs or UltraCaps).

The output is electronically protected against overload, no-load, and short-
circuits. If there is a protection event, audible noise may occur.

(1) At heavy overloads (when output voltage falls below 13V), the power supply delivers 

continuous output current for 2…5 s. After this, the output is switched off for approximately 
7 s before a new start attempt with duration of 1 s is automatically performed. This cycle is 
repeated as long as the overload exists. If the overload has been cleared, the device operates 
normally. 

Attributes

Values

Notes

Output voltage 

Nom 

DC 24V 

Adjustment range 

Min 24…28V 

Guaranteed 

value 

Max 30V 

This is the max output voltage that can occur at the clockwise end position of the potentiometer 
due to tolerances. It is not guaranteed that this value can be achieved. 

Factory settings 

Typ 

24.1V 

±0.2%, at full load and cold unit 

Line regulation 

Max 

10 mV 

Between 90V and 300V AC 

Load regulation 

Max 

100 mV 

Between 0 A and 20 A, static value, see 

Figure 7

 

Ripple and noise voltage 

Max 

100 mVpp 

Bandwidth 20 Hz to 20 MHz, 50 Ohms 

Output current 

Nom 

20.0 A 

At 24V and an ambient temperature below 55 °C (131 °F)

Nom 

12.5 A 

At 24V and 70 °C (158 °F) ambient temperature 

Nom 

17.1 A 

At 28V and an ambient temperature below 55 °C (131 °F)

Nom 

10.7 A 

At 28V and 70 °C (158 °F) ambient temperature 

Derate linearly between 55…70 °C (131…158 °F)

Overload behavior 

Continuous current 

For output voltage above 13V DC, see 

Figure 7

 

Intermittent current

(1)

For output voltage below 13V DC, see 

Figure 7

 

Overload/ short-circuit current 

Max 

27.5 A 

Continuous current, see 

Figure 7

 

Typ 30 

Intermittent current peak value for 1 s typ
Load impedance 50 mOhm, see 

Figure 8

 Discharge current of output capacitors is not included. 

Max 

11 A 

Intermittent current average value (R.M.S.) Load impedance 50 mOhm, see 

Figure 8

 

Output capacitance 

Typ 

6 800 μF 

Included inside the power supply 

Back-feeding loads 

Max 

35V 

The unit is resistant and does not show malfunctioning when a load feeds back voltage to the 
power supply. It does not matter whether the power supply is on or off. The absorbing energy 
can be calculated according to the built-in large sized output capacitor. 

Figure 7 - Output voltage vs. output current, typ

Figure 8 - Short-circuit on output, intermittent current, typ

Output voltage

30 A

24V

Output current

13V

0V

5 A

10 A

15 A

25 A

0 A

Adjustment range

28V

A

B

20 A

A: continuous current
B: intermittent current

 

Output
Current

0

30 A

7 s

7 s

7 s

1 s

1 s

2-5 s

t

Short -circuit

Normal

operation

Normal

operation

First
pulse

 

Summary of Contents for 1606-XLB480E

Page 1: ...Basic Power Supply 24V 20 A 480 W Single phase Input Catalog Number 1606 XLB480E Reference Manual Original Instructions...

Page 2: ...y Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written per...

Page 3: ...als 13 Lifetime Expectancy 13 Mean Time Between Failure 13 Electromagnetic Compatibility 14 Environment 15 Safety and Protection Features 16 Dielectric Strength 17 Approvals and Fulfilled Standards 18...

Page 4: ...4 Rockwell Automation Publication 1606 RM104A EN P July 2020 Table of Contents Notes...

Page 5: ...monitoring can help to avoid long downtimes Power supply features AC 100 240V Wide range Input Active Power Factor Correction PFC Width only 59 mm 2 32 in Efficiency up to 95 3 Safe HiccupPLUS Overlo...

Page 6: ...equency 50 60 Hz 6 AC Input current 4 3 2 3 A At 120 230V AC Power factor 0 99 0 97 At 120 230V AC AC Inrush current 15 35 A pk At 120 230V AC 40 C 104 F cold start Efficiency 94 2 95 3 At 120 230V AC...

Page 7: ...s Notes AC 100V AC 120V AC 230V Input current Typ 5 2 A 4 3 A 2 3 A At 24V 20 A see Figure 3 Power factor Typ 0 99 0 99 0 97 At 24V 20 A see Figure 4 Crest factor Typ 1 6 1 7 2 0 At 24V 20 A The crest...

Page 8: ...n Attributes Values Notes AC 100V AC 120V AC 230V Inrush current Max 15 A pk 18 A pk 42 A pk At 40 C 104 F cold start Typ 13 A pk 13 A pk 25 A pk At 25 C 77 F cold start Typ 13 A pk 15 A pk 35 A pk At...

Page 9: ...gulation Max 100 mV Between 0 A and 20 A static value see Figure 7 Ripple and noise voltage Max 100 mVpp Bandwidth 20 Hz to 20 MHz 50 Ohms Output current Nom 20 0 A At 24V and an ambient temperature b...

Page 10: ...e Figure 9 Min at 24V 10 A 44 ms 44 ms 44 ms See Figure 9 Typ at 24V 20 A 27 ms 27 ms 27 ms See Figure 9 Min at 24V 20 A 22 ms 22 ms 22 ms See Figure 9 Figure 9 Hold up time vs input voltage Figure 10...

Page 11: ...10 A 25 at 15 A 25 at 20 A Power losses Typ 5 7 W 4 6 W 3 5 W At 24V 0 A Typ 15 6 W 14 8 W 13 2 W At 24V 10 A Typ 32 8 W 29 6 W 23 7 W At 24V 20 A Figure 12 Efficiency vs output current at 24V typ Fig...

Page 12: ...L N DC OK Contact DC OK Status Indicator DC ok Relay Figure 17 Front side User Elements 1 Input Terminals N L Line input PE Protective Earth input 2 Output Terminals Two identical poles and two identi...

Page 13: ...s the mean time to failure MTTF value is the same value as the MTBF value Attributes Input Output DC OK Signal Type Screw termination Screw termination Push in termination Solid wire 6 mm2 max 0 0093...

Page 14: ...EN 61000 4 6 0 15 80 MHz 20V Criterion A Mains voltage dips EN 61000 4 11 0 of 100V AC 0V AC 20 ms Criterion A 40 of 100V AC 40V AC 200 ms Criterion C 70 of 100V AC 70V AC 500 ms Criterion A 0 of 200V...

Page 15: ...ages 4 kV according to overvoltage category III Input to PE According to IEC 60664 1 for altitudes up to 2000 m 6560 ft Degree of pollution 2 According to IEC 60664 1 not conductive Vibration sinusoid...

Page 16: ...9 Over temperature protection Included Output shutdown with automatic restart Temperature sensors are installed on critical components inside the unit and turn off the unit in safety critical situatio...

Page 17: ...he value in the table below We recommend that either the pole or the pole shall be connected to the protective earth system This helps to avoid situations in which a load starts unexpectedly or cannot...

Page 18: ...Use Particular requirements for control equipment Applicable for US and Canada E File NMTR 7 E56639 Ind Cont Eq Regulation Name Regulation Symbol Notes CE EU Declaration of Conformity Trade conformit...

Page 19: ...5 mm 0 30 or 0 59 in Housing material Body Aluminum alloy Cover Zinc plated steel Installation clearances 40 mm 1 57 in on top 20 mm 0 79 on the bottom 5 mm 0 20 in left and right side If the adjacent...

Page 20: ...d even if there is a short circuit across the output It requires suitable power supplies on the input where the sum of the continuous short circuit current stays below 26 A This is typically achieved...

Page 21: ...ncrease the output ampacity or the hold up time For longer hold up times the 1606 XLSBUFFER24 might also be an option Series Operation Devices of the same type can be connected in series for higher ou...

Page 22: ...bient temperatures up to 70 C 158 F Leakage current EMI inrush current and harmonics increase when using multiple devices Recommendations for building redundant power systems Use separate input fuses...

Page 23: ...d in the middle of the box no other heat producing items are inside the box The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1 cm...

Page 24: ...24 Rockwell Automation Publication 1606 RM104A EN P July 2020 Notes...

Page 25: ...and dispose of equipment Industrial Components Preventive Maintenance Enclosures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial a...

Page 26: ...Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation inst...

Reviews: