Environment

Switching Frequencies

PFC converter 

80...130 kHz 

Input voltage and load dependent 

Main converter 

75...180 kHz 

Output voltage and load dependent 

Auxiliary converter  60 kHz 

Fixed frequency 

Attributes

Values

Notes

Operational temperature 

-25…+70 °C (-13…+158 °F) 

Operational temperature is the same as the ambient or surrounding 
temperature and is defined as the air temperature 2 cm (0.79 in.) 
below the unit. 

Storage temperature 

-40…+85 °C (-40…+185 °F) 

For storage and transportation 

Output derating 

12 W/°C (12 W/1.8 °F),
30 W/1000 m (30 W/3281 ft),
or 5 °C/1000 m (9 °F/3281 ft)

Between 55…70 °C (131…140 °F)
For altitudes >2000 m (6560 ft), see 

Figure 19

 

The derating is not hardware-controlled. You have to take this into consideration to stay below the 
derated current limits in order not to overload the unit. 

Humidity 5...95% 

r.h. According to IEC 60068-2-30 

Atmospheric pressure 

110…54 kPa 

See 

Figure 19

 for details 

Altitude 

Up to 5000 m (16,400 ft) 

See 

Figure 19

 for details 

Overvoltage category 

II 

According to IEC 60664-1, for altitudes up to 5000 m (16,400 ft)

Impulse withstand voltages 

4 kV (according to overvoltage 
category III) 

Input to PE According to IEC 60664-1, for altitudes up to 2000 m 
(6560 ft)

Degree of pollution 

According to IEC 60664-1, not conductive 

Vibration sinusoidal 

2…17.8 Hz: ±1.6 mm (0.06 in.);
17.8…500 Hz: 2 g (19.61 m/s

2

)

2 hours / axis 

According to IEC 60068-2-6 

Shock 

30 g 6 ms, 20 g 11 ms
3 bumps per direction,
18 bumps in total 

According to IEC 60068-2-27 

Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 
mm (0.59 in.) and a thickness of 1.3 mm (0.05 in.) and standard orientation.

LABS compatibility 

As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is 
suitable for use in paint shops. 

Corrosive gases 

Tested according to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a 
service life of 10 years min in these environments. 

Audible noise 

Some audible noise may be emitted from the power supply during no load, overload, or short circuit. 

Figure 18 - Output current vs. ambient temp.

Figure 19 - Output current vs. altitude

0

0

+70 °C

20 A

+55

Allowed Output Current at 24V

12.5 A

Ambient Temperature

-25

 

2000 m

5000 m

18.8 A

16.3 A

20.0 A

Altitude

Allowed Output Current at 24V

B

A

AP

*)

80 kPa

54 kPa

110 kPa

0 m

*) Atmospheric pressure

A... Tamb < 45 °C
B... Tamb < 55 °C

4000 m

62 kPa

 

Summary of Contents for 1606-XLB480E

Page 1: ...Basic Power Supply 24V 20 A 480 W Single phase Input Catalog Number 1606 XLB480E Reference Manual Original Instructions...

Page 2: ...y Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written per...

Page 3: ...als 13 Lifetime Expectancy 13 Mean Time Between Failure 13 Electromagnetic Compatibility 14 Environment 15 Safety and Protection Features 16 Dielectric Strength 17 Approvals and Fulfilled Standards 18...

Page 4: ...4 Rockwell Automation Publication 1606 RM104A EN P July 2020 Table of Contents Notes...

Page 5: ...monitoring can help to avoid long downtimes Power supply features AC 100 240V Wide range Input Active Power Factor Correction PFC Width only 59 mm 2 32 in Efficiency up to 95 3 Safe HiccupPLUS Overlo...

Page 6: ...equency 50 60 Hz 6 AC Input current 4 3 2 3 A At 120 230V AC Power factor 0 99 0 97 At 120 230V AC AC Inrush current 15 35 A pk At 120 230V AC 40 C 104 F cold start Efficiency 94 2 95 3 At 120 230V AC...

Page 7: ...s Notes AC 100V AC 120V AC 230V Input current Typ 5 2 A 4 3 A 2 3 A At 24V 20 A see Figure 3 Power factor Typ 0 99 0 99 0 97 At 24V 20 A see Figure 4 Crest factor Typ 1 6 1 7 2 0 At 24V 20 A The crest...

Page 8: ...n Attributes Values Notes AC 100V AC 120V AC 230V Inrush current Max 15 A pk 18 A pk 42 A pk At 40 C 104 F cold start Typ 13 A pk 13 A pk 25 A pk At 25 C 77 F cold start Typ 13 A pk 15 A pk 35 A pk At...

Page 9: ...gulation Max 100 mV Between 0 A and 20 A static value see Figure 7 Ripple and noise voltage Max 100 mVpp Bandwidth 20 Hz to 20 MHz 50 Ohms Output current Nom 20 0 A At 24V and an ambient temperature b...

Page 10: ...e Figure 9 Min at 24V 10 A 44 ms 44 ms 44 ms See Figure 9 Typ at 24V 20 A 27 ms 27 ms 27 ms See Figure 9 Min at 24V 20 A 22 ms 22 ms 22 ms See Figure 9 Figure 9 Hold up time vs input voltage Figure 10...

Page 11: ...10 A 25 at 15 A 25 at 20 A Power losses Typ 5 7 W 4 6 W 3 5 W At 24V 0 A Typ 15 6 W 14 8 W 13 2 W At 24V 10 A Typ 32 8 W 29 6 W 23 7 W At 24V 20 A Figure 12 Efficiency vs output current at 24V typ Fig...

Page 12: ...L N DC OK Contact DC OK Status Indicator DC ok Relay Figure 17 Front side User Elements 1 Input Terminals N L Line input PE Protective Earth input 2 Output Terminals Two identical poles and two identi...

Page 13: ...s the mean time to failure MTTF value is the same value as the MTBF value Attributes Input Output DC OK Signal Type Screw termination Screw termination Push in termination Solid wire 6 mm2 max 0 0093...

Page 14: ...EN 61000 4 6 0 15 80 MHz 20V Criterion A Mains voltage dips EN 61000 4 11 0 of 100V AC 0V AC 20 ms Criterion A 40 of 100V AC 40V AC 200 ms Criterion C 70 of 100V AC 70V AC 500 ms Criterion A 0 of 200V...

Page 15: ...ages 4 kV according to overvoltage category III Input to PE According to IEC 60664 1 for altitudes up to 2000 m 6560 ft Degree of pollution 2 According to IEC 60664 1 not conductive Vibration sinusoid...

Page 16: ...9 Over temperature protection Included Output shutdown with automatic restart Temperature sensors are installed on critical components inside the unit and turn off the unit in safety critical situatio...

Page 17: ...he value in the table below We recommend that either the pole or the pole shall be connected to the protective earth system This helps to avoid situations in which a load starts unexpectedly or cannot...

Page 18: ...Use Particular requirements for control equipment Applicable for US and Canada E File NMTR 7 E56639 Ind Cont Eq Regulation Name Regulation Symbol Notes CE EU Declaration of Conformity Trade conformit...

Page 19: ...5 mm 0 30 or 0 59 in Housing material Body Aluminum alloy Cover Zinc plated steel Installation clearances 40 mm 1 57 in on top 20 mm 0 79 on the bottom 5 mm 0 20 in left and right side If the adjacent...

Page 20: ...d even if there is a short circuit across the output It requires suitable power supplies on the input where the sum of the continuous short circuit current stays below 26 A This is typically achieved...

Page 21: ...ncrease the output ampacity or the hold up time For longer hold up times the 1606 XLSBUFFER24 might also be an option Series Operation Devices of the same type can be connected in series for higher ou...

Page 22: ...bient temperatures up to 70 C 158 F Leakage current EMI inrush current and harmonics increase when using multiple devices Recommendations for building redundant power systems Use separate input fuses...

Page 23: ...d in the middle of the box no other heat producing items are inside the box The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of 1 cm...

Page 24: ...24 Rockwell Automation Publication 1606 RM104A EN P July 2020 Notes...

Page 25: ...and dispose of equipment Industrial Components Preventive Maintenance Enclosures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial a...

Page 26: ...Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installation inst...

Reviews: