Publication 1404-UM001D-EN-E - October 2004
A-24
Powermonitor 3000 Data Tables
Table A.16 Selftest/Diagnostic Results
CSP File No.
N22
Remote I/O BT
36
CIP Assy. Inst.
23
No. of Elements
27
User Configurable
No
Data Type
Integer
Data Access
Read only
PM3000 Type
All
Element
No.
Modbus
Address
Element name
Range
Comment
0
30601
Bulletin number
1404
1
30602
Series
0 to 8
0 = A, 1 = B, etc.
2
30603
Overall status
-
0 = OK
3
30604
Data Acquisition status
-
0 = OK
bit 0 = overall status; 0 = pass, 1 = fail
bit 1 = reserved
bit 2 = data bus connection failure
bit 3 = address test failure
4
30605
Data FLASH status
-
0 = OK
5
30606
Real-time clock status
-
0 = OK
6
30607
RTC NVRAM status
-
0 = OK
Non-zero indicates corruption of non-volatile memory. This
does not cause product to shutdown. The error is cleared on a
reset/power cycle. If this error is detected, date/time, and
energy values are reset.
7
30608
Option communications status -
0 = OK or no optional communications present
8
30609
Display module status
-
0 = OK or no DM connected
9
30610
Watchdog status
-
0 = OK
10
30611
Code FLASH status
-
0 = OK
bit 0 = overall status; 0 = pass, 1 = fail
bit 1 = boot code checksum failure
bit 2 = application code checksum failure
bit 3 = calibration CRC failure
bit 4 = no calibration data
bit 5 = wrong application firmware loaded
11
30612
RAM status
-
0 = OK
bit 0 = read/write test failure
12
30613
Application FRN
0 to 9999
100 indicates V1.00, 103 indicates V1.03, etc.
13
30614
Boot code FRN
0 to 9999
100 indicates V1.00, 101 indicates V1.01, etc.
14
30615
ASIC build #
0 to 9999
Revision number of the ‘code’ which was used to fabricate the
ASIC.
15
30616
Option communications FRN
0 to 9999
100 indicates V1.00, 103 indicates V1.03, etc. 0 = none (catalog
numbers ending in -000, -232)
16
30617
Display module FRN
0 to 9999
104 indicates V 1.04, 105 indicates V1.05, etc.
Returns 0 if no DM connected
17
30618
Reserved 0
Returns
0
Summary of Contents for 1404-M4
Page 6: ...Publication 1404 UM001D EN E October 2004 Table of Contents 4 ...
Page 26: ...Publication 1404 UM001D EN E October 2004 2 14 Product Description ...
Page 264: ...Publication 1404 UM001D EN E October 2004 C 10 Sample Applications ...
Page 278: ...Publication 1404 UM001D EN E October 2004 C 24 Sample Applications ...
Page 279: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 25 Allen Bradley HMIs ...
Page 280: ...Publication 1404 UM001D EN E October 2004 C 26 Sample Applications ...
Page 285: ...Publication 1404 UM001D EN E October 2004 Sample Applications C 31 Allen Bradley HMIs ...
Page 304: ...Publication 1404 UM001D EN E October 2004 D 6 Technical Specifications ...
Page 324: ...Publication 1404 UM001D EN E October 2004 F 18 Powermonitor 3000 EtherNet IP Device Profile ...
Page 340: ...Publication 1404 UM001D EN E October 2004 G 16 Powermonitor 3000 ControlNet Device Profile ...
Page 354: ...Publication 1404 UM001D EN E October 2004 6 Index ...
Page 355: ...Allen Bradley HMIs ...