AHE00047EN 2001
19
Alfa LU-VE is a trademark registered and owned by LU-VE Group.
Alfa LU-VE reserves the right to change specifications without prior notification.
Black: 230 VAC, 50-60 Hz
Blue: Neutral
Green/Yellow: Protective earth
Blue: GND - Control interface
Yellow: Control input 0-10V or PWM
Red: Voltage 10V (1.1 mA)
White: Tach output
Electrical connection for 1-4 EC fan motors 1-phase with 0-10V speed regulation
High speed setting
The “High speed” setting provides the maxi-
mum fan speed according to datasheet. This is
achieved when a jumper connects the +10 V
output of the fan motor to the inlet signal (see
electrical scheme).
If continuous rpm modulation is needed, the
jumper should be removed and replaced by an
external signal (between 0 and 10 V max). The
jumper connection can be made in the connec-
tion box or inside each fan motor’s “black box”.
Low speed setting
The “Low speed” setting provides the reduced
fan speed according to datasheet. This is
achieved with a resistance kit reducing the steer-
ing signal from 10 V to 6.7 V. The fan will oper-
ate at a fixed rpm value.
If continuous rpm modulation is needed, the
resistance kit should be removed and replaced
by an external signal (between 0 and 6.7 V
max).
This resistance kit is located inside the connec-
tion box (if selected) or inside each fan motor’s
“black box”.
L
N
PE
+10V
0-10V
GND
-M1
L
N
PE
+10V
0-10V
GND
-M2
L
N
PE
+10V
0-10V
GND
-M3
L
N
PE
+10V
0-10V
GND
-M4
L
N PE
10V
SN 0V
Signal box
BK
BN
GN
YE
BK
BN
GN
YE
BK
BN
GN
YE
BK
BN
GN
YE
BU
GY
BK
GY
BK
GY
BK
GY
BK
Jumper connection for fixed high fan speed.
Replace with 6.7V resistance for low fan speed
or external signal for rpm modulation.
Jumper
Resistance kit
10V
Axial-lead resistor 0.25W
SN
0V
3.9 k
Ω
±5%
6.8 k
Ω
±5%