Alfa Laval Kolding A/S, www.alfalaval.com
Mounting instructions
9611-99-5749, Indication unit for LKLA ø85, PNP, Alfa Laval pinout (ZZ0495)
Replacing
9612-5106-13, Hall prox. switch unit LKLA ø85, PNP (Grey) 20-30VDC
9612-5106-15, Hall prox. switch unit LKLA ø85, PNP (Green) 5-24VDC
►
Loosen the screws (1) and remove the
angle bracket.
►
Mount the puck as shown (2).
►
Attach the puck and the angle bracket (3).
Pointer showing to the right: Valve is closed.
The drawing on the right shows basically an
NC (Normally Closed) valve.
Puck pointer must therefore be installed to the
right so that it follows the valve closed direc-
tion.
2
1
3
►
Keep a distance of approx. 2 mm between
puck and angle bracket.
Note: Most of the actuators are delivered with
a coupling provided with a rim. It ensures
the right distance between puck and angle
bracket.
►
Tighten the screws (1).
►
Tighten opposite grub screws (2) on the
puck, tightening torque 2 Nm.
2 mm
2
1
1
Wiring (PNP, Alfa Laval pin connection)
Closed: OUT +2 (A2) Pin 3
Open: OUT +1 (A1) Pin 2
Electrical design DC PNP
Operating voltage 10...36 V DC
Output function 2 x NO
Current consumption < 15 mA
Current rating 250 mA
Ambient temperature -25...80 °C
Protection rating IP 67
2:
L-
L+
BN
1
2
WH
BK
BU
4
3
2
1
3:
A2
A1
4
3
2
1
Items supplied
1 x puck E17013
1 x inductive double sensor IN5416
2 x hexagon head screws
4 x washers