Setting the Airflow
Twist the rotating adjustment ring until
the desired airflow is reached. Reference
the correlation table at right and printed
on the device. No tools required.
Correlation Table
MR MODULO
AIRFLOW & ZONE CONTROL
ADJUSTABLE CONSTANT AIRFLOW REGULATOR
IOM
READ AND SAVE THESE INSTRUCTIONS
1 Ø
Ø
Ø
3 Ø
m
3
/h CFM
K
100
59
J
110
65
I
120
71
H
130
76
G
140
82
E
150
88
C
160
94
A
190 112
P/N: 11016310
Ø 5" (125 mm)
60-110 CFM
(100-190 m
3
/h)
m
3
/h CFM
U
225 132
S
250 147
Q
275 160
N
300 177
M
325 191
J
350 206
D
400 235
P/N: 11016313
Ø 8" (200 mm)
m
3
/h
CFM
U
300
175
R
355
205
O
400
235
L
450
265
I
500
295
G
550
325
A
650
385
P/N: 110163114
Ø 10" (250 mm)
P/N: 11016308
Ø 4" (100 mm)
m
3
/h CFM m
3
/h CFM
L
15
9
-
-
J
20
12
-
-
H
25
15
-
-
F
30
18
-
-
E
35
21
70
41
D
40
24
75
44
C
45
26
80
47
A
55
32
90
53
P/N: 11016309
Ø 5" (125 mm)
10-50 CFM (15-85 m
3
/h)
m
3
/h CFM m
3
/h CFM
L
15
9
-
-
I
25
15
-
-
G
-
-
60
35
F
30
18
65
38
D
-
-
70
41
C
-
-
75
44
B
45
26
80
47
A
50
29
85
50
P/N: 11016311
Ø 6" (150 mm)
m
3
/h
CFM
R
100
60
P
110
65
O
120
70
M
130
75
L
140
80
K
150
90
J
160
95
m
3
/h
CFM
H
170
100
G
180
105
F
190
110
E
200
120
D
210
125
A
240
140
Certain letters correspond to two setpoints: one with the clip, and one without the clip.
11016307
Ø 3" (80 mm)
m
3
/h CFM m
3
/h CFM
K
20
12
-
-
J
25
15
-
-
H
30
18
-
-
G
35
21
45
26
F
40
24
50
29
B
45
26
60
35
SMALL DIAMETERS
LARGE DIAMETERS
EXHAUST AIR
SUPPLY AIR
Installation
•
The MR Modulo will push-fit into circular ducts in close proximity to a take-off or terminal.
•
Orient the MR Modulo according to the airflow direction indicated on the device.
•
Horizontal or vertical mounting is acceptable.
•
To avoid acoustic and aeraulic disturbance, provide the following distance between the
device and the terminal
(grille / diffuser / inlet):
•
Exhaust Air: 1x the device diameter Ø
•
Supply Air: 3x the device diameter Ø
360°