Alderon Industries Vizzyalarm VZW-02 Operation, Maintenance And Installation Manual Download Page 3

Alderon Industries, LLC - Leading Edge Control Products  |  218.483.3034  |  [email protected]  |  [email protected]  |  alderonind.com

Installation Instructions | Page 3

(Fig. 7; auxiliary contacts)

(Fig. 9)

Auxiliary Contacts:

Terminals AUX

Connects to external monitoring device

Normally Open; Single Pole, Single Throw

30VDC, 700mA maximum

Note: The auxiliary dry contacts of the alarm panel are normally open ONLY, 

recommended to use 18 gauge 2-conductor wire. Used for remote monitoring.

Sensor/Signaling Device:

Terminals ALARM

Zone-1 Alarm

Normally Open or Normally Closed

3-10VAC/DC, 10mA minimum

Note: Use normally open sensors (signaling device) for high level alarm indication 

and normally closed sensors (signaling device) for low level alarm indication.

3. If connecting to an existing alarm security system or building automation system (BAS), use 18 gauge 2-conductor wire to 

  connect the existing product to the AUX inputs on the terminal block (Fig. 7). See below for wiring information. The 

  auxiliary contacts are activated when the sensor (signaling device) contacts are “closed” during an alarm condition 

  (normally open or normally closed). When connected, run the wire(s) towards the bottom/center of the alarm panel to go 

  through the wiring access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).

4. Connect the sensor (signaling device) to the ALARM inputs on the terminal block (Fig. 8). See below for wiring 

  information. The alarm is activated when any “dry” type sensor that “closes” during an alarm condition (normally open or 

  normally closed). When connected, run the wire(s) towards the bottom/center of the alarm panel to go through the wiring 

  access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).

Note: When installing a sensor or device, always refer to its installation instructions for complete operating information.

CAUTION:

 Route all wires away from sharp objects and internal components when installing wires.

Installation of the Alarm Panel 

(continued)

5. After the wiring is completed and before replacing the enclosure cover, run the wire(s) towards the bottom/center of the 

  alarm panel to go through the wiring access hole once the enclosure cover is replaced (Fig. 9 and Fig. 10).

CAUTION:

 Route all wires away from sharp objects and internal components when installing wires.

(Fig. 10)

Vizzyalarm™ 1-Zone WiFi Alarm Panel - Installation Instructions

(Fig. 8; sensor/signaling device)

(BAS)

(ALARM)

Summary of Contents for Vizzyalarm VZW-02

Page 1: ...y open or normally closed Installing 3 AA batteries not included provides battery backup during power outages Use the auxiliary contacts to connect to building automation systems BAS and phone dialers Multiple sensors signaling device can be connected for expanded monitoring An alarm condition occurs when the sensor signaling device contact is activated during which the red alarm LED will illumina...

Page 2: ...silence pushbutton for longer than 5 6 seconds along with the buzzer quick pulse tone will change the low battery alarm enable or disable setting approximately 9 10 seconds total elapsed time See complete user guide for settings information and page 4 to test auxiliary contacts separately WARNING Do not connect AC power from a standard wall outlet or receptacle to the alarm panel until all steps o...

Page 3: ...lly open or normally closed When connected run the wire s towards the bottom center of the alarm panel to go through the wiring access hole once the enclosure cover is replaced Fig 9 and Fig 10 4 Connect the sensor signaling device to the ALARM inputs on the terminal block Fig 8 See below for wiring information The alarm is activated when any dry type sensor that closes during an alarm condition n...

Page 4: ...nel The green power LED should illuminate solid when powered Fig 11 Fig 13 Fig 12 Fig 11 Installation of the Alarm Panel continued 1b Test the alarm panel by activating the sensor signaling device Fig 13 The alarm LED should illuminate solid buzzer should annunciate solid and auxiliary contacts should activate Press the test silence pushbutton and the buzzer should silence while the alarm LED rema...

Page 5: ...nect pushbutton for less than 5 seconds or until the blue WiFi LED flashes quickly Fig 16 Then release the WiFi connect pushbutton and use a mobile phone laptop or computer that is within range of the alarm panel to pair the device with an IP address Note Once the alarm panel has been placed into the HTTP mode there is approximately 2 minutes to establish a connection with the preferred electronic...

Page 6: ...ig 21 TEST SILENCE 2 If you are a new user you will be automatically directed to the device registration page once signed in to the account If you already have an account with one 1 or more devices click tap Register New Device for additional devices Enter your Vizzy ID VID number which is located on the inside cover of the alarm panel enclosure Fig 21 After entering your VID number click tap the ...

Reviews: