Page 2 | Installation Instructions
1. To install/replace the included LiPo battery for the backup power feature, remove the enclosure cover (Fig. 1) and install
the 3.7VDC LiPo battery (model LP683857) by plugging the quick connect of the battery wires into the battery power
receptacle of the alarm panel (Fig. 2). Make sure to have the proper orientation of the quick connect (notch up, pins down)
to ensure a secure connection. After installing the battery, the green power LED should illuminate (slow flash). To perform
a quick test, press and hold the test/silence pushbutton (Fig. 2 and Fig. 3) to activate the alarm. If properly installed, all
of the LEDs should illuminate (quick flash) and then after approximately 5-6 seconds, the buzzer should annunciate
(quick pulse). Immediately release the test/silence pushbutton after the buzzer annunciates a quick pulse tone to end the
test. Leave the enclosure cover off until both step 3 and step 4 are completed for sensor and auxiliary contact wiring.
CAUTION:
Holding the test/silence pushbutton for longer than 5-6 seconds along with the buzzer quick pulse tone will
change the temperature alarm enable or disable setting (approximately 9-10 seconds; total elapsed time). See complete
user guide for settings information and page 4 to test auxiliary contacts separately.
WARNING:
Do not connect AC power from a standard wall outlet or receptacle to the alarm panel until all steps of the
installation are complete and the system is ready for testing.
Installation of the Alarm Panel
Vizzyalarm™ 3-Zone WiFi Alarm Panel - Installation Instructions
Vizzyalarm™ 3-Zone WiFi Alarm Panel - Installation Instructions
2. Determine the mounting location for the alarm panel and leave the enclosure cover off. Make sure power outlet (120VAC,
50/60 Hz) is within 5-feet of the alarm panel (Fig. 4). The power outlet should be on a separate circuit breaker from any
other device and not on a switched receptacle to maintain system integrity. Mount the alarm panel using two (2) #6
self-tapping screws (not included / Fig. 5). Use two (2) #8 plastic anchors (not included / Fig. 6) if mounting the alarm
panel to sheet rock.
(Fig. 3)
(Fig. 2)
(Fig. 1)
(Fig. 6)
(Fig. 5)
(Fig. 4)
5 ft. Max
2A = Rechargeable Battery
2B = Battery Quick Connect
2C = Battery Power Receptacle
2D = Test/Silence Pushbutton
2E = Power LED
(green)
2F = Alarm LEDs (3)
(red)
2G = Vizzy/WiFi LED
(blue)
2H = Alarm Buzzer
2A
2F
2E
2B
2C
2D
2G
2H