POWER SOURCE

G N L1

WIRE USING

JUNCTION BOX

120 VAC

G T2 T1

G

BLACK

WHITE

RED

PUMP

G L2 L1

230 VAC

G T2 T1

G

BLACK

WHITE/RED

RED

POWER SOURCE

WIRE USING

JUNCTION BOX

PUMP

ProbeX™

Power Cable

ProbeX™

Power Cable

(Fig. 6)

RubberLox™

Power Cable

(120VAC example shown)

5. Excess cable should be neatly bundled and secured with the 

included RubberLox™ adjustable strap and remaining between 

the bracket (Fig. 6). CAUTION! Do not secure probe cables next 

to the power cable as magnetic interference while the pump is 

running may interfere with the liquid detection electronics and 

may cause erratic operation such as continuous pump running.

6. For piggyback plug models, plug the pump power cable into the female piggyback plug on the ProbeX™ pump 

switch (Fig. 7A), and then plug the male end of the piggyback plug into the receptacle (voltage depends on model; 

Fig. 7B). After the pump and piggyback plugs are connected to a receptacle, see page 4 for testing.

7. For hardwire models connecting to a pump, 120VAC models see figure 8 and 230VAC models see figure 9.

Installation of the ProbeX™ Continued

Alderon Industries  •  PO Box 827  Hawley, MN 56549  •  P: 218-483-3034  •  F: 218-483-3036  •  alderonind.com

Installation Instructions | Page 3

ProbeX

 - Installation Instructions