Alarmtech PSV 2465-40 Instruction Manual Download Page 2

 

© 2016 Alarmtech – 

www.alarmtech.se

  

2 / 4 

PSV 2650-40 manual 1636en 

1.

 

INSTALLATION 

50

50

50

335

435 (440 with lid)

4

2

0

 (

4

2

5

 w

it

h

 l

id

)

40

3

3

0

Ø14

Battery #1

12 V, 40 Ah

+

-

Battery #2

12 V, 40 Ah

+

-

Cable between batteries

Battery cable (+)

Battery cable (-)

230 VAC

Outputs

Case 
fixing 

hole

Case fixing hole

Case fixing hole

Grounding 

cable

Ø8

All dimensions in [mm]

To front panel

Ø8

PE

N

Case 
fixing 

hole

L

Mains 

input

Power Unit 

PSV 2465

Main output fuse

6.3 A, fast

Signalling 

outputs

Mains input fuse 

2.5A, slow

Output & battery 

connector

Battery fuse

10 A, fast

Optional Fuse Card

PSV FC24-6

 

Power supply installation and start-up procedure: 

 

Break-out pre-cut openings on top side of the case and install 
cable glands: one for 230 VAC input on the left side and 
planned number (1 to 5) for output cables 

 

Fix unit in destination place using 4 fixing holes 

 

Place two batteries 12 V/40 Ah in battery chambers 

 

Make internal connection in battery pack connecting left bat-
tery (+) with right battery (-) with the help of grey cable 

 

Make connection between left battery (-) and battery con-
nector using black battery cable connected to BAT- 

 

Make connection between right battery (+) and battery con-
nector using red battery cable connected to +BAT 

 

Make appropriate connections between power outputs and 
power receivers - carry out to the load using necessary num-
ber of outputs and cable glands 

 

The socket outlet delivering 230 VAC shall be installed near 
the power supply unit and shall be easily accessible 

 

Make sure that cable delivering 230VAC to PSV 2465-40 is dis-
connected from mains 

 

Carry in cable delivering 230 VAC to the unit using separate 
cable gland on the left side and connect it to 230 VAC input of 
power unit PSV-2465 – make sure that PE cable is connected 
to PE input 

 

Switch on mains delivering energy to power supply  - PSV 
2465-40 unit will start automatically delivering power to the 
load and monitoring state of PS

 

 

Reviews: