© 2016 Alarmtech –
www.alarmtech.se
2 / 4
PSV 2650-40 manual 1636en
1.
INSTALLATION
50
50
50
335
435 (440 with lid)
4
2
0
(
4
2
5
w
it
h
l
id
)
40
3
3
0
Ø14
Battery #1
12 V, 40 Ah
+
-
Battery #2
12 V, 40 Ah
+
-
Cable between batteries
Battery cable (+)
Battery cable (-)
230 VAC
Outputs
Case
fixing
hole
Case fixing hole
Case fixing hole
Grounding
cable
Ø8
All dimensions in [mm]
To front panel
Ø8
PE
N
Case
fixing
hole
L
Mains
input
Power Unit
PSV 2465
Main output fuse
6.3 A, fast
Signalling
outputs
Mains input fuse
2.5A, slow
Output & battery
connector
Battery fuse
10 A, fast
Optional Fuse Card
PSV FC24-6
Power supply installation and start-up procedure:
Break-out pre-cut openings on top side of the case and install
cable glands: one for 230 VAC input on the left side and
planned number (1 to 5) for output cables
Fix unit in destination place using 4 fixing holes
Place two batteries 12 V/40 Ah in battery chambers
Make internal connection in battery pack connecting left bat-
tery (+) with right battery (-) with the help of grey cable
Make connection between left battery (-) and battery con-
nector using black battery cable connected to BAT-
Make connection between right battery (+) and battery con-
nector using red battery cable connected to +BAT
Make appropriate connections between power outputs and
power receivers - carry out to the load using necessary num-
ber of outputs and cable glands
The socket outlet delivering 230 VAC shall be installed near
the power supply unit and shall be easily accessible
Make sure that cable delivering 230VAC to PSV 2465-40 is dis-
connected from mains
Carry in cable delivering 230 VAC to the unit using separate
cable gland on the left side and connect it to 230 VAC input of
power unit PSV-2465 – make sure that PE cable is connected
to PE input
Switch on mains delivering energy to power supply - PSV
2465-40 unit will start automatically delivering power to the
load and monitoring state of PS