series with every input, if you don
’t connect the sensor to the input, please
connect a 2.2K
resistor in series to instead. Moreover, only the digital
detector, NC type, can be used in EOL mode. Please see the below diagram.
4) If you setup the input type as NO, then please keep the two points of the
inputs free and the sensor type must be NO. Please see the below diagram.
5) The Unit built-in 240VAC@3A rated relay. Please make sure the power cord
is rated while you connect to equipment device. Please make sure the power
consumption is less than 250W. If you need heavy equipment, please
connect an additional relay.
6) The R1+ and R1- is for alarm-link output, when the system alarms, it will
close for 4 minutes, the rated output power is 700W. If you need heavily
equipment, please connect an additional relay.
7) The R2+ and R2- is the relay output for SMS command. CC is close, DD is
open, EE is inquiry the status.
8) The +12VDC is for the detectors, if the detectors need 12VDC power, then
please connect it to the +12VDC. The 12VDC power is from external power,
not from the backup battery. So please note: When AC power failure, the
+12VDC point will not supply power.