background image

the unit to a wall or other flat surface using the hardware 
provided (see page 4 for printed template).   

  As shown in Fig. 2, the rear housing includes two mount-

ing holes for single-gang (

A

) and four mounting holes for 

double-gang (

B

) electrical utility boxes, as well as four all-

purpose holes (

C

) for mounting to drywall or other surfac-

es (use minimum #6 screws suitable for the surface).    

 
 

"

EXPANDER GROUP" DIALS  

  Inside the Expander are 2 rotary dials (see Fig. 3).  These 

dials are used to set the "Expander Group".  All version 2 
Gateways include an identical set of dials.  

Therefore, the 

dial values set on your Gateway MUST then match the dial 
values set on your AL-IME2-EXP 

Expanders.   

IMPORTANT:  Each Gateway in your system MUST be 
set to a different "Expander Group" value along with its asso-
ciated Expanders.  The "Expander Group" dial setting deter-
mines which Expanders are associated with which Gateway, 
thus preventing Gateways from discovering unintended Ex-
panders.   

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 
  Expander Group values of "

00

" through "

99

" are valid selec-

tions.   

 

 

IMPORTANT:  

The small "selection arrow" on each dial 

must be pointing directly to the desired Group value.  In Fig. 
4 (below), the Group value is set to "

50

".  Use a small flat-

head screwdriver to turn the dials and make the selections.   

Be sure to orient the Expander as shown above with the RE-
SET  
button ABOVE the dials to ensure proper Group 
setting! 

 
 
 
 
 
 
 
 
 
 
 
 
 

POWER UP 

  Connect the 6VAC power transformer wires (non-polarized).  

Upon power up:   

 Red LED solid (momentarily) 

 Yellow LED blinks (counting out "Expander Group" dial 

setting).   

Note: 

 Zero = No blink 

 Yellow LED solid + green LED flickering rapidly 

 

  Next, reset the Expander as follows:   

 

 

Reset the Expander 

 

IMPORTANT:

  Before securing the Expander housing 

cover, 

ALWAYS 

reset the Expander memory, even if the 

Expander is new "out of the box" and/or has never been 
used previously.   

  After initial power up, press and hold the "RESET" button 

(see below for location); continue to hold the button until the 
red light turns on solid.  Now, release the button and the 
green light will flicker rapidly

.   

 

  This "resetting" of the Expander clears all memory and en-

sures that any previous data is cleared from the unit.   

 

Note: 

 Resetting the Expander also re-writes the 

"Expander Group" dial setting into the Expander memory.   

 
 

EXPANDER LED INDICATIONS  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

CLOSE HOUSING COVER  

  Close the housing cover by first engaging the hooks at the 

top, then snapping the bottom together.  Secure the cover 
with the Bottom Screw provided as shown in Fig. 5.   

 
 
 
 
 
 
 
 
 
 
 
 
 

Congratulations!  You're finished! 

 Now go to the DL-

WINDOWS™ for Networx™ V5 USER'S GUIDE (OI383) for 
instructions about discovering your Expanders from DL-
Windows. 

Fig. 5:  Bottom Screw 

Fig. 3:  "RESET" button and two "Expander Group dials"  

Be sure to orient the Expander with the RESET button ABOVE 

the dials as shown above to ensure proper Group setting ! 

RESET 

button 

Expander 

Group  

Dials  

Yellow  

On Power up, displays "Expander Group" dial setting (in 

two sequences) 

Receiver On (normal operation) 

Red 

Transmitter on 

(Expander Status) 

Not configured - Rapid blinking / flickering 

Idle / configured - 1 blink per second 

Lock Communication Fail - 2 blinks (continuously)  

Expander Communication Fail - 4 blinks (continuously)  

Green  

Fig. 4.  Example:  The above Expander Group dials are set to "50" 

"selection 

arrow" 

"selection 

arrow" 

Summary of Contents for Trilogy Networx AL-IME2-EXP

Page 1: ...ge Networx 75 175 ArchiTech Networx 50 125 Note Actual range varies with building con struction AL IME2 EXP Expander Installation Instructions ALARM LOCK 2018 WI2156BLF 1 18 Gateway Expander to Expander Clear field range 500 Typical indoor range 75 175 Note Actual range varies with building construction AL RADIO LINK 900 MHz GFSK 50 Channels 10mW power output POWER Provided by UL Listed Class 2 Tr...

Page 2: ...pander installation location We recommend obtaining or creating a layout of your intended system identifying all proposed installation lo cations also noting building construction materials IMPORTANT Be sure to read the EXPANDER GROUP DIALS section on page 3 before powering your Expanders The above guidelines and tips should be followed for each additional Expander added to the system See next sec...

Page 3: ...l setting Note Zero No blink Yellow LED solid green LED flickering rapidly Next reset the Expander as follows Reset the Expander IMPORTANT Before securing the Expander housing cover ALWAYS reset the Expander memory even if the Expander is new out of the box and or has never been used previously After initial power up press and hold the RESET button see below for location continue to hold the butto...

Page 4: ...anty contains the entire warranty It is the sole warranty and any prior agreements or representa tions whether oral or written are either merged herein or are expressly cancelled ALARM LOCK neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall ALARM LOCK be li...

Reviews: