54
5. COMMISSIONING THE APPLIANCE
The following operations must be carried out by professionally quali-
fied personnel, registered in accordance with current legislation.
Commissioning of the appliance by an unauthorized company or un-
authorized people invalidates the guarantee.
Alarko Carrier does not take any responsibility for the damage or
injury on persons, animals or objects caused by commissioning by
unauthorized people.
6. PERIODIC MAINTENANCE AND CLEANING
6.1 Periodic Maintenance of the Combi Boiler (Authorized
Service)
During and also after guarantee period you must keep taking maintenance once
a year (before winter) to provide safe use, fuel saving and long service life.
All maintenance operations must be carried out by professionally
qualified personnel, authorized by Alarko Carrier.
In order to guarantee the long life of the appliance and in accordance
with the current gas safety regulations, only use original spare parts.
Alarko Carrier does not take any responsibility for the damage or
injury on persons, animals or objects caused by maintenance by un-
authorized people or service.
6.2 Maintenance Content
Maintenance includes below points:
•
Main heat exchanger cleaning
•
Control of burner and electrode
•
Fan motor balance control and fin cleaning
•
Control of thermostat and sensors
•
Cleaning of siphon
•
Control of condensate water drain
•
Control of expansion tank pressure, filling if low
•
Control of flue leak proofing
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
21
INSTALLATION INSTRUCTIONS
TA99A086.B0706
15
3.5 Gas connection
The connection to the gas supply must be carried out by professionally qualified personnel, registered
in accordance with current legislation.
When connecting the boiler to the gas supply pipe, only use appropriate gas fittings in accordance
with the Gas Safety and Use Regulations..
Before installing the boiler, check the following:
�
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
�
The gas supply line must be a minimum of a 22mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
�
Check the internal and external seals of the gas supply system.
�
A gas shut-off valve must be installed upstream of the appliance
�
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
�
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
�
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.
�
Conversion of the appliance from natural gas to LPG or vice versa must be carried out by qualified personnel.
3.6 Electrical connections
The connection to the mains power supply must be carried out by professionally qualified personnel,
registered in accordance with current legislation and authorised by Radiant Bruciatori.
Always check to make sure that the appliance has an efficient earth system. This requirement is only
satisfied if it has been properly connected to an efficient earth system installed in accordance with the
requirements of current safety standards (Standard CEI 64-8 Electrical Installations).
This basic safety
measure must be checked and verified.
In case of doubt, have the electrical system checked by a qualified electrician. The manufacturer will not be
held liable for any damage or injury caused as a result of an inefficient or inexistent earth system.
�
The boiler functions with an alternating current of 230 V and 50 Hz and has maximum power absorption of 180
W.
The appliance should be protected by a 3 A
fuse. The connection to the mains electricity supply must be
via a single-pole switch, with at least 3 millimetres gap between open contacts, mounted upstream of the
appliance. Make sure that the positions of the live and neutral wires correspond to the wiring diagram.
�
Ensure the domestic power supply is checked by a qualified electrician to ensure that it can support the
maximum power absorption of the appliance, as indicated on the rating plate. In particular, make sure that the
cable sizes are adequate for the power absorbed by the appliance.
�
The power supply cable must not be replaced by the user. if the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified electrician.
�
When replacing the power supply cable, only use cables of the same characteristics (HO5 VV-F 3x1) with
maximum external Ø 8 mm;
When using an electrical appliance, a few fundamental rules must be observed:
�
Do not touch the appliance with damp or wet parts of the body or when barefoot.
�
Do not pull on the electric wires.
�
Do not leave the appliance exposed to atmospheric elements (rain, sun, etc,) unless these conditions have been
expressly provided for.
�
Do not allow the appliance to be used by children or anyone unfamiliar with its operation.
Alarko Carrier.
3.3 Electrical Connection
110
3.2 Gas Connection
Summary of Contents for SRS 20
Page 1: ...SERADENS SUPER SRS 20 28 36 PREMIX CONDENSING BOILER INSTALLATION AND OPERATING INSTRUCTIONS ...
Page 2: ...Code No A 1 4 8i Publishing Date 100616 Revision Date 100616 ...
Page 27: ...27 3 2 Dimensions SRS 20 28 36 Figure 5 Dimensions ...
Page 37: ...37 Figure 13 Opening the Package Opening the Package ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 ...