Appendix B Configuration parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
34
34
No
Name
Parameter
Valid value
Meaning
Config-
urator
Display
4…20 mA
0…20 mA
0…5 mA
0…1 V
RTD 100M (GOST)
RTD 53M (GOST)
TC type S
TC type R
TC type N
TC type J
TC type А-1
PL-2 / Control channels
1
C.SP
Setpoint
-
999…9999*
2
HYSt
Hysteresis
0,001…9999*
3
C.SP.o
Manual setpoint change (
±)
0…9999*
4
Ht.on
ON-state minimum duration
0…9000
5
Ht.oF
OFF-state minimum dura-
tion
0…9000
6
dL.on
Turn-on delay
0…3600
7
dL.oF
Turn-off delay
0…3600
8
bL.St
Ignore alarm on start
ON
OFF
9
AL.t
Logic unit function
0
Measuring mode
1
Heating
2
Cooling
3
Alarm within limits
4
Alarm outside limits
5
Retransmission
10
Er.St
Error output state
ON
OFF
11
C.in
Logic unit input
0
OFF
1…8
d1
…d8 (input 1…8)
9
F1 (average 1
…2)
10
F2 (average 1
…3)
11
F3 (average 1
…4)
12
F4 (average 1
…5)
13
F5 (average 1
…6)
14
F6 (average 1
…7)
15
F7 (average 1
…8)
16
A1 (difference 1-2)
17
A2 (difference 3-4)
18
A3 (difference 5-6)
19
A4 (difference 7-8)
20…27
r1…r8 (rate of
change 1…8)**