![Akytec MU210-410 User Manual Download Page 9](http://html1.mh-extra.com/html/akytec/mu210-410/mu210-410_user-manual_2887630009.webp)
8
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
2 Specifications
2.1 Specifications
Table 2.1 Specifications
Denomination
Value
Power supply
Power supply
24 (10 … 48) V DC
Power consumption
5 W
Protection against reverse polarity of
supply voltage
Yes
Interfaces
Data transfer interface
Dual Port Ethernet 10/100 Mbit
Configuration interface
USB 2.0 (MicroUSB), Ethernet 10/100 Mbit
Date transfer protocol
Modbus TCP
Protocol version
IPv4
Digital outputs
Number of outputs
16 (2 groups of 8 outputs)
Output type
Transistor switch
Operation mode
– switching of a logic state;
– low-frequency PWM signal generation;
– high frequency PWM signal generation (first 8 outputs
only);
– generation of a given number of pulses (only the first 3
outputs)
Output switching mode
High-side switch
Push-pull output
Output power supply
10…36 V
Maximum DC load current
0.8 A
0.1 A
Maximum allowed short-time output
current
1.3 A
0.19 A
Maximum output frequency (for
resistive load)
10,000 Hz
60,000 Hz
Minimum duration of output signal (for
resistive load)
10 µs
1 µs
Maximum load capacity
1 µF with a load resistance of at least 500 Ω
Output protection type
– protection against short circuit when switching on;
– protection against low and high voltage power outputs;
– protection against overheating of the output stage;
– output overcurrent protection;
– self-induction reverse current protection
Flash-memory (log-file)
Number of write and erase cycles
Up to 100,000
Maximum log file size
2 KB
Maximum number of log files
1000
Minimum log writing interval
10 s
Real time clock
Inaccura-
cy
at +25 °C
max. 3 s per day
over the entire temperature
range
max. 10 s per day
Battery type
CR2032