34
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Load
resistance,
R
L
Load capacity, C
L
0 pF
1000 pF
22 nF
50 nF
100 nF
1µF
5 kΩ
1
1
4
10
30
100*
* With a load capacity of 1 µF and a load resistance of 5 kΩ:
– maximum pulse rise time is 10 µs,
– maximum pulse decay time is 20 µs
The maximum allowable frequency of the PWM at the outputs supply voltage of 24 V when operating
at resistive and capacitive loads is given in
:
Table 5.11 Maximum allowable PWM frequency (Hz)
Load
resistance,
R
L
Load capacity, C
L
0 pF
1000 pF
22 nF
50 nF
100 nF
1µF
250 Ω
60,000
50,000
14,000
6,000
3,000
200
500 Ω
60,000
60,000
31,000
13,500
6,500
500
5 kΩ
60,000
60,000
50,000
35,000
17,000
1 000
5.8.2 High-side switch mode
The minimum pulse duration at the outputs supply voltage of 24 V, depending on the resistive and
capacitive loads, is given in
below:
Table 5.12 Minimum pulse duration of the output signal in the high-side switch mode (µs)
Load
resistance,
R
L
Load capacity, C
L
0 pF
1000 pF
22 nF
50 nF
100 nF
1µF
50 Ω
10
10
15
25
40
—
500 Ω
10
10
30
50
400
1500
5 kΩ
10
20
300
500
5000
10000
* With a load capacity of 1 µF and a load resistance of 5 kΩ:
– maximum pulse rise time is 10 µs,
– maximum pulse decay time is 20 µs
The maximum frequency of the PWM at the outputs supply voltage of 24 V when operating at
resistive and capacitive loads is given in
Table 5.13 Maximum PWM frequency (Hz)
Load
resistance,
R
L
Load capacity, C
L
0 pF
1000 pF
22 nF
50 nF
100 nF
1µF
50 Ω
10,000
1 000
650
400
250
—
500 Ω
10,000
1 000
300
200
25
5
5 kΩ
10,000
500
30
20
2
1
5.9 Output operation on inductive load
Module outputs can be connected to an inductive load. The module implements hardware protection
against self-induction current that occurs during load shedding. An external protective diode
connection is not required.