Fig. 7.1   Operation display 

Each segment corresponds to 10% of the measurement range. 

In case of a fault in the 4-20 mA and 2-10 V input circuit (short circuit or sensor break), the 
three right and left extreme segments flash in red (Fig. 7.2) and the output is set to the state 
defined in the parameter 

3. “Output safe state” (Table 6.2). 

 

Fig. 7.2   Fault indication

 

For signals 0-20 mA and 0-10 V, short circuit and sensor break are indicated as 0%. The 
output will not be set to the safe condition. 

If the indication does not correspond to the real process value or when indicating an error, 
check the set signal type matches the real signal (Table 6.2, parameter 1).

 

8.  Maintenance 

The device is maintenance free. 

If necessary, the device should be cleaned with a damp cloth only. No abrasives or solvent-
containing cleaners may be used. 

9.  Transportation and storage 

Pack the device in such a way as to protect it reliably against impact for storage and 
transportation. The original packaging provides optimum protection. 

If the device is not taken immediately after delivery into operation, it must be carefully stored 
at a protected location. The device should not be stored in an atmosphere with chemically 
active substances. 

Permitted storage temperature: -

25…+55 °C 

 

NOTICE 

The device may have been damaged during transportation. 
Check the device for transport damage and completeness! 
Report the transport damage immediately to the shipper and akYtec GmbH! 

 

 

Summary of Contents for ITP15

Page 1: ...Vahrenwalder Str 269 A 30179 Hannover Germany Tel 49 0 511 16 59 672 0 www akytec de ITP15 LED Bargraph Indicator User guide ITP15_2019 12_48199_EN All rights reserved Subject to technical changes an...

Page 2: ...iew 2 2 Technical data 2 2 1 Galvanic isolation 2 2 2 Environmental conditions 2 3 Intended use 3 4 Functions 3 5 Installation 3 5 1 Wiring 3 5 1 1 Input 4 5 1 2 Output 4 6 Configuration 5 6 1 Alarm l...

Page 3: ...sis 1 Display events signal 0 signal 0 0 signal 100 signal 100 signal 100 fault Enclosure for panel mounting horizontal or vertical Dimensions 48 x 26 x 65 mm Weight max approx 30 g 2 1 Galvanic isola...

Page 4: ...roper installation can cause serious or minor injuries and damage the device Installation must be performed only by fully qualified personnel The device is designed for horizontal or vertical panel mo...

Page 5: ...line and electric fuse I 0 5 A The maximum conductor cross section is 1 mm Wires should be stripped for approx 8 10 mm 5 1 1 Input Fig 5 5 Input wiring Table 5 1 Terminal assignment Designation Descri...

Page 6: ...1 Table 6 1 Function buttons Button Description Press 3 s start alarm limits adjustment Press 1 s save the parameter and go to the next one Increase value Press 3 s start configuration Press 1 s decre...

Page 7: ...put safe state On Off 4 Flashing Off On 6 1 Alarm limits The alarm limits are the signal levels at which the segment color changes and the output switches on or off depending on the value of the param...

Page 8: ...ons and then press to save and quit Fig 6 4 a b If you need only one limit lower or upper press and hold the button for 3 seconds set the first or the last segment to slow flashing green using the but...

Page 9: ...an error check the set signal type matches the real signal Table 6 2 parameter 1 8 Maintenance The device is maintenance free If necessary the device should be cleaned with a damp cloth only No abras...

Page 10: ...any Tel 49 0 511 16 59 672 0 www akytec de 9 10 Scope of delivery ITP15 1 Gasket 1 Mounting nut 1 User guide 1 Appendix A Dimensions Fig A1 Fig A2 To prevent the device spinning the borehole in the fr...

Reviews: