Aksa DSE 7320 AMF Operating Manual Download Page 25

1. DSE 7320 AMF CONTROL MODULE

AUTO

DEEP SEA ELECTRONICS

DSE 7320

DSE

AUTO

DEEP SEA ELECTRONICS

DSE 7320

DSE

1

Transfer to generator 

(manual mode only)

Start engine (when in 

manual mode)

Mute alrm / Lamp test

Mains Available LED.

On when the mains  is within 

limits and able to take load.

Close Mains LED.

On when the generator is 

required to be on load.

Close Generator LED

On when the generator is 

required to be on load.

Generator Available 

LED. On when the 

generator is within limits 

and able to take load.

Menu navigation 

buttons

Transfer to mains 

(manual mode only)

Main status and 

instrumentation display

Four configurable 

LEDs

Select stop mode

Select manual mode

Select test on load mode

Select auto mode

Summary of Contents for DSE 7320 AMF

Page 1: ...AUTO DEEP SEA ELECTRONICS DSE 7320 DSE DSE 7320 AMF DSE 7320 AMF KONTROL MOD L ALI TIRMA EL K TABI DSE 7320 AMF CONTROL MODULE OPERATING MANUAL...

Page 2: ...4212 G ne li Ba c lar STANBUL T 90 212 478 66 66 F 90 212 657 55 16 e mail aksa aksa com tr YETK L SERV S AKSA SERV S K RALAMA Muratbey Beldesi G ney Giri i Caddesi No 8 34540 atalca STANBUL T 90 212...

Page 3: ......

Page 4: ...ARI 6 7 ALARM KAYIT DEFTERININ G STERILMESI 7 8 OPERASYON 8 8 1 OTOMATIK OPERASYON 8 8 2 MANUEL OPERASYON 9 8 3 TEST OPERASYONU 10 9 ORTAKLI ALI TIRMA 11 10 KORUMALAR 11 10 1 KAZ ALARMLARI 12 10 2 ANA...

Page 5: ...D ebeke normal iken yanar ebeke devrede LED y k ebekeden beslendi inde yanar Jenerat r devrede LED y k jenerat rden beslendi inde yanar Jenerat r haz r LED jenerat r normal iken yanar 1 DSE 7320 AMF K...

Page 6: ...ICS DSE 7320 DSE AUTO DEEP SEA ELECTRONICS DSE 7320 DSE 2 nce man el konumunu se in sonra start tu una basarak motoru mar lay n stop tu una bas l rsa jenerat r durdurulur 1 1 MOTORUN ALI TIRILMASI 1 2...

Page 7: ...l kontrol edilir Mod l man el konumuna al nd nda ve start butonuna bas ld nda motor mar yap l r ve y ks z olarak al t r l r Mod l uzak start sinyali ald nda veya ebeke enerjisi kesildi inde transfer a...

Page 8: ...a bak labilir Start Bu buton sadece STOP RESET veya MANUEL konumunda etkindir MANUEL veya test konumunda bu butona bas ld nda jenerat r y ks z olarak MANUEL veya y kl olarak test al acakt r STOP RESET...

Page 9: ...otomatik sayfa kayd rma iptal edilir G sterge sayfas ba l n kayd rmak otomatik sayfa kayd rmay etkin hale getirmek i in tu una veya tu una bas l r Sayfa kayd rma el ile yap ld nda zaman ayarlar n pane...

Page 10: ...yap lm oldu u zaman Jenerat r o Jenerat r Voltaj faz N o Jenerat r Voltaj faz faz o Jenerat r Frekans o Jenerat r Ak m o Jenerat r Toprak Ak m o Jenerat r Y k kW o Jenerat r Y k kVA o Jenerat r G Fakt...

Page 11: ...r Kay t defterinde sadece durdurma ve elektriksel a t rma alarmlar tutulur ikaz alarmlar tutulmaz Kay t defteri doldu unda ve herhangi durdurma alarm meydana geldi inde en eski kay tl alarm giri i si...

Page 12: ...evcut ise motorun yak t yolunu a ma bobinine enerji g nderilir ve dizel motor mar yap l r NOT nite CAN i in programlanm ise ECU Start komutunu CAN vas tas yla alacakt r E er motor mar lama esnas nda a...

Page 13: ...ildi inde jenerat r otomatik start yap lmayacakt r Start i leminin ba lamas i in butonu na bas n z ALI TIRMA SIRASI NOT Bu i letme konumunda start gecikme s resi yoktur Yak t yolunu a ma bobinine ener...

Page 14: ...ise ECU Start komutunu CAN vas tas yla alacakt r E er motor mar lama esnas nda al maz ise mar motoru devreden kar ve bir sonraki mar lamaya kadar 1 3 sn bekler sonra 2 kez tekrar mar lan r Motora en...

Page 15: ...rlanm egzersiz al ma program n n etkin olmas ile O Yedekli ift al ma sisteminde Ana Yedek emas na g re program n tamam ayr ayr al r Her iki jenerat r al r fakat sadece birisi y k zerine al r NOT T m a...

Page 16: ...a durma talimat verildi inde motorun al ma a devam etti i tespit edilirse NOT Stop Ar zas ya bas n alg lay c s n n ar zal oldu unu g sterebilir Motoru durdurup ya alg lay c n n devresini kablosunu kon...

Page 17: ...ayarlanm n alarm seviyesini a d mod l taraf ndan tespit edildi inde Mod l motor su s cakl n mod l program nda ayarlanm n alarm seviyesinin alt na d t n tespit etti inde Motor h z mod l program nda aya...

Page 18: ...f rlanabilmektedir E er all warnings are latched t m ikazlar kilitlensin opsiyonu se ili ise man el olarak s f rlama reset yap lana kadar kaz uyar s silinemez 10 4 DURURMA ALARMLARI Durdurma alarmlar...

Page 19: ...ri a t nda Jenerat r k voltaj mod l program nda ayarlanm de erden a a ya d t nde Ya bas n sens r ba lant s alg lanamad a k devre Kullan c taraf ndan durdurma olarak ayarlanabilen giri lerdir kullan c...

Page 20: ...elikle jenerat r zerindeki y k kald r r ve so utma s resi devreye girer ve s renin sonunda jenerat r durdurulur Alarm silinmeli ve hata ortadan kald r ld ktan sonra mod l s f rlanmal d r Reset rne in...

Page 21: ...17 11 7320 AMF KONTROL MOD L KABLOLAMASI...

Page 22: ...212 G ne li Ba c lar STANBUL T 90 212 478 66 66 F 90 212 657 55 16 e mail aksa aksa com tr AUTHORIZED SERVICE AKSA SERVICE RENTAL Muratbey Beldesi G ney Giri i Caddesi No 8 34540 atalca STANBUL T 90 2...

Page 23: ...carefully before starting to use your Generator Set This manual gives general information about operation of the generator set Never operate maintain or repair your generator set without taking genera...

Page 24: ...EVENT LOG 7 8 OPERATION STAND ALONE 8 8 1 AUTOMATIC MODE OF OPERATION 8 8 2 MANUAL OPERATION 9 8 3 TEST MODE OF OPERATION 10 9 OPERATION DUAL MUTUAL STANDBY 11 10 PROTECTIONS 11 10 1 WARNINGS 12 10 2...

Page 25: ...n limits and able to take load Close Mains LED On when the generator is required to be on load Close Generator LED On when the generator is required to be on load Generator Available LED On when the g...

Page 26: ...S DSE 7320 DSE AUTO DEEP SEA ELECTRONICS DSE 7320 DSE 2 First select manual mode then press the start button to crank the engine Select Stop Reset mode The generator is stopped 1 1 STARTING THE ENGINE...

Page 27: ...nual control of the generator functions Once in Manual mode the module will respond to the start button start the engine and run off load If the engine is running off load in the Manual mode and a rem...

Page 28: ...scription of Test Operation elsewhere in this manual Start This button is only active in STOP RESET or MANUAL mode Pressing this button in manual or test mode will start the engine and run off load ma...

Page 29: ...truments on the currently selected page press the scroll or buttons The autoscroll is disabled To re enable autoscroll press the or buttons to scroll to the title of the instrumentation page ieEngine...

Page 30: ...ECU Generator o Generator Voltage ph N o Generator Voltage ph ph o Generator Frequency o Generator Current o Generator Earth Current o Generator Load kW o Generator Load kVA o Generator Power Factor o...

Page 31: ...s Once the log is full any subsequent shutdown alarms will overwrite the oldest entry in the log Hence the log will always contain the most recent shutdown alarms The module logs the alarm along with...

Page 32: ...e If a start request is still present at the end of the start delay timer the fuel relay is energised and the engine will be cranked NOTE If the unit has been configured for CAN compatible ECU s will...

Page 33: ...utton confirms this action Manual mode allows the operator to start and stop the set manually and if required change the state of the load switching devices WAITING IN MANUAL MODE When in manual mode...

Page 34: ...ate test mode be pressing the pushbutton An LED indicator beside the button confirms this action Test mode will start the set and transfer the load to the generator to provide a Test on load function...

Page 35: ...both modules are controlled by the same remote start signal In this instance the Master will start its generator Should the Master fail the Slave will be instructed to start and take the load If the M...

Page 36: ...n critical alarm conditions and do not affect the operation of the generator system they serve to draw the operators attention to an undesirable condition Example In the event of an alarm the LCD will...

Page 37: ...are latched will cause warning alarms to latch until reset manually If the module is configured for CAN and receives an error message from the engine control unit Can ECU Warning is shown on the modul...

Page 38: ...e module Example NOTE The alarm condition must be rectified before a reset will take place If the alarm condition remains it will not be possible to reset the unit The exception to this is the Low Oil...

Page 39: ...lectrical trip alarm depending upon module configuration High current shutdown is a latching alarm and stops the Generator Remove the fault then press Stop Reset to reset the module NOTE Higher overlo...

Page 40: ...16 Electrical trips are latching alarms and stop the Generator Remove the fault then press Stop Reset to reset the module...

Page 41: ...17 11 7320 AMF CONTROLLER WIRING...

Page 42: ...4 62 461 82 82 F 0232 462 24 63 462 24 40 KAYSER OSMAN KAVUNCU BULVARI NO 207 H MEL KGAZ T 0352 331 97 77 78 F 0352 331 97 71 D YARBAKIR ERGAN YOLU 1 KM 1 SAN S T CAM KAR ISI ASTAY PLAZA YEN EH R T 04...

Page 43: ...Road Bardon Hill Coalville Leicestershire LE67 ISZ U Kingdom T 44 0 1530 837 472 F 44 0 1530 519 577 e mail sales aksa uk com U S A Aksa USA 371 Exchange Street West Monroe LA 71292 T 1 318 855 83 77...

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ......

Page 50: ...0 971 4 880 91 41 Evren Mah Camii Yolu Cad No 5 34212 G ne li Ba c lar stanbul N CHINA No 19 Tongjiang Road New District Changzhou Jiansu Zone China T 86 0 519 856 01 307 F 86 0 519 851 50 132 e mail...

Reviews: