2
2. CONTROLS
Stop / Reset
This button places the module into its
Stop/Reset
mode. This will clear any alarm conditions for which the
triggering criteria have been removed. If the engine is running and the module is in Stop mode, the module will
automatically instruct the changeover device to unload the generator. The fuel supply de-energises and the engine
comes to a standstill. Should a
remote start signal
be present while operating in this mode, a remote start will
not occur.
Manual
This mode allows manual control of the generator functions. Once in
Manual mode
the module will respond to
the start button, start the engine, and run off load. If the engine is running off-load in the
Manual mode
and
a
remote start signal
becomes present, the module will automatically instruct the changeover device to place
the generator on load (‘Close Generator’ becomes active (if used)).
Upon removal of the remote start signal, the generator remains on load until either selection of the
‘
STOP/RESET
’ or ‘
AUTO
’ modes.
Auto
This button places the module into its ‘
Automatic
’ mode. This mode allows the module to control the function
of the generator automatically. The module will monitor the remote start input and mains supply status and once
a start request is made, the set will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from the generator and shut
the set down observing the stop delay timer and cooling timer as necessary. The module will then await the
next start event
Test
This button places the module into its ‘
Test
’ mode. This allows an on load test of the generator.
Once in
Test mode
the module will respond to the start button, start the engine, and run on load.
Start
This button is only active in STOP/RESET or MANUAL mode.
Pressing this button in manual or test mode will start the engine and run off load (manual) or on load (test).
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test feature.
Scroll
This buttons scrolls through the instruments in the currently displayed page
Page
Toggles the display between instrumentation an event log mode,