Initial configuration
The
AKO-16526
controller can be adapted to different types of installation according to the different options chosen
in the set-up wizard.
Before completing the wiring, make sure you are familiar with the details of the installation in order to configure it
correctly.
It is advisable to note the following points:
Compressor
Whether the controller should switch the compressor on and off (InI=2, 3, 5, 6, 7 or 8) or whether the compressor is
switched on and off by the low pressure switch (InI=1 or 4).
Defrost
Defrosting method used:
Electric (InI=1, 2 or 3)
Air (evaporator fans) (InI=4, 5 or 6)
Hot gas valve (condensing unit) (InI=7 or 8)
Solenoid/EEV
Type of solenoid/EEV used:
• So thermostatic expansion valve (u00=0).
• PWM-controlled EEV (without liquid solenoid) (u00=1).
• Stepper-controlled EEV (u00=2). Requires an external controller for the EEV. For more information, please refer
to the
available on our website.
Options u00=1 and u00=2 require the use of a superheating temperature sensor (S5) and an evaporator pressure
sensor (S6).
Evaporator fans
If the fan control is ON/OFF (F10=0) or an external frequency inverter is used for ventilation (F10=1).
The second option is only available if a STEPPER-type electronic expansion valve (u00=2) is not used.
Analogue outputs
The analogue output (ANALOG OUT) enables communication between the controller and the external controller of
the electronic expansion valve (if u00=2), or with the frequency inverter of the fans (if F10=1), and can be configured
as 4-20 mA output (o30=0) or as 0-10 V output (o30=1).
Consult the specifications of the external controller or drive before setting this option.
SET POINT (temperature)
Make a note of the desired set temperature value.
If u00=1 or 2, you must also know:
Type of gas
Type of gas used in the installation.
u02=0
R404A
u02=1
R134A
u02=2
R407A
u02=3
R407F
u02=4
R410A
u02=5
R450A
u02=6
R513A
u02=7
R744
u02=8
R449A
u02=9
R290
u02=10
R32
u02=11
R448A
u02=12
R1234ze
u02=13
R23
u02=14
R717
u02=15
R407C
u02=16
1234yf
u02=17
R22
u02=18
R454C
u02=19
R455A
u02=20
R507A
u02=21
R515B
u02=22
R452A
u02=23
R452B
u02=24
R454A
Pressure sensor type
Type of evaporator pressure sensor installed:
4-20 mA (I61=1)
0-5 V (I61=2)
0.5-4.5 V (I61=3)
0-10 V (I61=4)
1-5 V(I61=5)
Note also the maximum and minimum values of the pressure sensor as well as the units of pressure used (bar or Psi).