Wiring
Always disconnect the power supply to do the wiring.
The probes and their cables must
NEVER
be installed in a conduit together with power, control or power
supply cables.
For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near the
device. The power supply cable shall be of the H05VV-F or NYM 1x16/3 type. The section to be used will depend
on current local regulations, but should never be less than 1.5 mm
2
.
Cables for relay or contactor outputs should have a section of 2.5 mm
2
, allow working temperatures equal to or
over 70ºC, and be installed with as little bending as possible.
The 120 / 230 V~ wiring area must be kept clear of any other external element.
The wiring setup depends on the options selected in the set-up wizard (See page 11) and on
the input and output configurations (See page 39).
Check the enclosed schematic and the defined configuration before wiring.
IMPORTANT:
• AUXILIARY relays are programmable, and their operation depends on the configuration.
• The function of the digital inputs depends on the configuration.
• The recommended currents and powers are the maximum working currents and powers.