7 - RELAYS R1 AND R2 OPERATION AND CONTROL

Thermostat relay R1

Thermostat relay R2

P11=Parameter 11, Set Point

P20=Parameter 20, Set Point

6 - DESCRIPTION OF PARAMETERS AND MESSAGES

The values in the Def column are factory-set.

www.ako.com

HOJA TÉCNICA

1472H206

Edición 01

(02 de 02)

351472206 REV. 00   2003

D.L.: B-33.359-03

8 - PARAMETERS TRANSFER

AKO-14916

Tabletop server which is connected by
means of the 

AKO-80018

, 230/12V, to the

power supply. Permit to transfer parameters
previously recorded in one server 

AKO-14918

, to other 

panel mounting

con-

trollers without these having to be powered.

AKO-14918

A portable server without supply to which
the parameters programmed in powered

AKO

controllers can be copied. The para-

meters may then be transferred from the ser-
ver to other identical powered units.

Start

Stop

P11+P13

TEMP.

P11

OFF

ON

P13

>

0

OFF

ON

P13

<

0

P11

Stop

Start

TEMP.

P11-P13

Operation for HEAT (P10=1)

Start

Stop

P20+P22

TEMP.

P20

OFF

ON

P22

>

0

OFF

ON

P22

<

0

P20

Stop

Start

TEMP.

P20-P22

Operation for HEAT (P19=1)

Stop

Start

P11+P13

TEMP.

P11

OFF

ON

P13

>

0

OFF

ON

P13

<

0

P11

Start

Stop

TEMP.

P11-P13

Operation for COLD (P10=0)

Stop

Start

P20+P22

TEMP.

P20

OFF

ON

P22

>

0

OFF

ON

P20

<

0

P20

Start

Stop

TEMP.

P20-P22

Operation for COLD (P19=0)

Parameters

Functions and description 

Values

Min.

Def.

Max.

01

Temperature display

(0 = Whole in ºC)  (1 = One decimal in ºC)

0

1

3

mode:

(2 = Whole in ºF)   (3 = One decimal in ºF)

02

Probe 1, input 

S1

Enable?

0=No 1=Yes 1=Yes

03

Probe 1, input 

S1

Calibration (Offset)

(ºC/ºF)

-20,0

0,0

20,0

04

Parameter 

03

adjustable by the user?

0=No 0=No 1=Yes

05

Probe 2, input 

S2

Enable?

0=No 1=Yes 1=Yes

06

Probe 2, input 

S2

Calibration (Offset)

(ºC/ºF)

-20,0

0,0

20,0

07

Parameter 

06

adjustable by the user?

0=No 0=No 1=Yes

08

Thermostat relay 

R1

,

Enable?

0=No 1=Yes 1=Yes

09

Thermostat relay 

R1

,

Probe selection

(0=S1- S2) (1=S1) (2=S2)

0

1

2

10

Thermostat relay 

R1

,

Operation type

(0=Cold) (1=Heat)

0

1

1

11

Thermostat relay 

R1

,

Set Point

(ºC/ºF)

-50,0

0,0

99,0

12

Parameter 

11

adjustable by the user?

0=No 1=Yes 1=Yes

13

Thermostat relay 

R1

,

Differential (Hysteresis)

(ºC/ºF)

-90,0

1,0

90,0

14

Parameter 

13

adjustable by the user?

0=No 1=Yes 1=Yes

15

Thermostat relay 

R1

,

Connection delay or protection

(min)

0

0

120

16

Parameter 

15

adjustable by the user?

0=No 1=Yes 1=Yes

17

Thermostat relay 

R2

,

Enable?

0=No

1=Sí 1=Yes

18

Thermostat relay 

R2

,

Probe selection

(0=S1- S2) (1=S1) (2=S2)

0

2

2

19

Thermostat relay 

R2

,

Operation type

(0=Cold) (1=Heat)

0

1

1

20

Thermostat relay 

R2

,

Set Point

(ºC/ºF)

-50,0

0,0

99,0

21

Parameter 

20

adjustable by the user?

0=No 1=Yes 1=Yes

22

Thermostat relay 

R2

,

Differential (Hysteresis)

(ºC/ºF)

-90,0

1,0

90,0

23

Parameter 

22

adjustable by the user?

0=No 1=Yes 1=Yes

24

Thermostat relay 

R2

,

Connection delay or protection

(min)

0

0

120

25

Parameter 

24

adjustable by the user?

0=No 1=Yes 1=Yes

26

Timing relay 

R1

,

Enable?

0=No 0=No 1=Yes

27

Timing relay 

R1

,

Elapsed time between starts

(h)

0

0

120

28

Parameter 

27

adjustable by the user?

0=No 1=Yes 1=Yes

29

Timing relay 

R1

,

Duration

(min)

0

0

120

30

Parameter 

29

adjustable by the user?

0=No 1=Yes 1=Yes

31

Timing relay 

R1

,

Relay status during P29

(0=OFF) (1=ON)

0

0

1

32

Timing relay 

R2

,

Enable?

0=No 0=No 1=Yes

33

Timing relay 

R2

,

Elapsed time between starts

(h)

0

0

120

34

Parameter 

33

adjustable by the user?

0=No 1=Yes 1=Yes

35

Timing relay 

R2

,

Duration

(min)

0

0

120

36

Parameter 

35

adjustable by the user?

0=No 1=Yes 1=Yes

37

Timing relay 

R2

,

Relay status during P35

(0=OFF) (1=ON)

0

0

1

38

Parameters transfer 

(0=disabled)  (1=send)  (2=receive)

0

0

2

39

Password to modify the configuration

0

0

126

40

Program version (information)

41

Display without pressing any key

1

1

4

42

Function by pressing UP key

0

2

7

43

Function by pressing UP key during 5”

0

4

7

44

Function by pressing DOWN key

0

0

7

45

Function by pressing DOWN key during 5”

0

3

7

46

Function by pressing UP + DOWN keys in panel mounting models

0

7

7

Function by pressing SET key in DIN rail models

The meaning for the options for parameters 41 to 46 is:
0=Key disabled

4=R2 Set Point display

1=Display Probe 1 of input S1

5=Start R1 timing

2=Display Probe 2 of input S

6=Start R2 timing

3=R1 Set Point display

7=Accessible parameters adjustment

Messages

_ _ _

Permanent

Probe S1 and Probe S2 disabled.

E1

Permanent

Probe S1 damaged (open, crossed circuit, temp. > 110ºC or  

temp. <-55ºC). Assigned relay OFF.

E2

Permanent

Probe S2 damaged (open, crossed circuit, temp. > 110ºC or 

temp.<-55ºC). Assigned relay OFF.

E1+E2 Flashing

Probes S1+S2 damaged (open, crossed circuit, temp. > 110ºC or

temp. <-55ºC). Relays R1 and R2 OFF.

EE

Permanent

Memory error

REMARK: When the time parameters are modified, the new values are applied once the current
cycle is completed. In order for it to have an immediate effect, switch the controller off and then
on again.

9 - MAINTENANCE

Clean the unit surface with a soft cloth and soap and water. Do not use abrasive detergents,
petrol, alcohol or solvents.

10 - WARNINGS

The use of the unit different to the manufacturer’s instructions voids the safety qualification.
To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should
be used.
Between -40 ºC and +20 ºC, when the probe is extended up to 1.000m with minimum 0,5mm

2

cable, deviation will be less than 0.25 ºC (probe extension cable ref. 

AKO-15586

).