6- DESCRIPTION OF PARAMETERS AND MESSAGES
The values in the
Def.
column are factory-set.
www.ako.com
HOJA TÉCNICA
1301H201
Edición 01
(02 de 02)
351301201 REV. 00 2004
D.L.: B-35.257-01
Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los descritos en nuestras hojas técnicas. Información actualizada en nuestra web
www.ako.com
8- RELAY OPERATION AND CONTROL
Operation for COLD (P0=0)
Operation for HEAT (P0=1)
7- PARAMETERS TRANSFER
AKO-14918
Thermometers parameters
Thermostats parameters
Functions and description
Values
Min.
Def.
Max.
C0
Sensor calibration (Offset)
( ºC)
-20
0
20
•
•
C1
Sensor differential (Hysteresis)
( ºC)
1
2
20
•
C2
Set Point upper limit
(It cannot be set above this value)
( ºC)
xx
99
99
•
C3
Set Point lowers limit
(It cannot be set below this value)
( ºC)
-50
-50
xx
•
C4
Compressor protection delay type: 0=OFF/ON (From the last switch-off) 1=ON (At switch-on)
0
0
1
•
C5
Protection delay time (Value for the option selected in parameter C4)
(min)
0
0
99
•
C7
Relay time in ON in case of faulty sensor
(If C7=0 and C8
≠
0, the relay will always be OFF disconnected)
(min)
0
10
99
•
C8
Relay time in OFF in case of faulty sensor
(If C8=0 and C7
≠
0, the relay will always be ON connected)
(min)
0
5
99
•
d0
Defrost frequency (Elapsed time between 2 starts)
(h)
0
1
99
•
d1
Defrost maximum duration
(min)
0
0
99
•
d2
Type of message during defrost:
(0=Current temperature display)
0
2
2
•
(1=Defrost start temperature display)
(2=Display dF message)
d3
Message maximum duration (Time added at the end of defrost)
(min)
0
5
99
•
L5
Access password to parameters
0
0
99
•
•
L6
Parameters transfer:
(0=Disabled)
(1=Send)
(2=Receive)
0
0
2
•
•
PU
Program version (Information)
•
•
P0
Type of operation:
(0=Cold)
(1=Heat)
0
0
1
•
P1
Delay of all functions on power supply switch on
(min)
0
0
99
•
P2
Allocation of password to Set Point: (0=Without allocation) (1=With allocation of L5 password)
0
0
1
•
P3
Initial parameters: (1=YES, configure to “Def” and exit programming if P2=0)
0
0
1
•
P5
Address for units with communication
0
0
99
•
•
P7
Temperature display mode: (0=Integers in ºC) (2=Integers in ºF)
0
0
2
•
•
EP
Exit programming
•
•
REMARK:
When the time parameters are modified, the new values are applied once the current cycle is completed. In order for it to have an immediate
effect, switch the controller off and then on again.
9- MAINTENANCE
Clean the controller surface with a soft cloth and soap and water. Do not use
abrasive detergents, petrol, alcohol or solvents.
10- WARNINGS
The use of the unit different to the manufacturer’s instructions voids the
safety qualification.
To ensure correct operation of the apparatus, only NTC type probes sup-
plied by AKO should be used.
Between -40 ºC and +20 ºC, when the probe is extended up to 1.000 m with
minimum 0,5 mm
2
cable, deviation will be less than 0.25 ºC (probe extension
cable ref.
AKO-15586
).
Messages
dF
It indicates defrosting is being carried out. In order to display “dF” during defrosting, it is essential that parameter d2 is set to option 2
E1
Sensor failure (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC)
_ _
Temperature > 99 ºF
EE
Memory failure
PA
Password request to enter in programming parameters or SET POINT
Portable server without supply, to which can be copied by transferred the
parameters programmed in a powered unit. The parameters may then be
transferred again from the server to other identical powered units.
To transfer parameters, other servers are available for controllers that should
be programmed identically in high quantity without power supply.
AKO-14918
Transfer
Power supply
Programming