![akira AC-S13CG series Service Manual Download Page 17](http://html.mh-extra.com/html/akira/ac-s13cg-series/ac-s13cg-series_service-manual_2885941017.webp)
17
1. Cooling
2. Dehumidifying
3. Heating
4. Auto
B. Input parameters
1. Indoor ambient temp. T in
2. Evaporator tube temp. T eva
3. Setting temp. T set
4. Condenser tube temp. T con
C. Targets
1. Indoor
motor
(motor)
2. Swing
motor
3. Outdoor motor (single speed motor)
4. Compressor
5. Four-way reversing valve
6. Cooling, dehumidifying indicator; running indicator
7. Digital tube setting temp. indicator or timer indicator
D. Fundamental functions
Cooling mode
1
The running conditions and control measures
a. If T in > or = T set + 1
o
C, the machine runs at the cooling mode. Compressor runs,
outdoor motor runs at low speed , indoor fan runs at the set fan speed.
b. If T in < or = T set –1
o
C , the machine stops. Compressor stops first, outdoor motor
stops after 15 seconds , indoor motor runs at the set fan speed.
c. If T set –1
o
C < T in < T set +1
o
C ,keep the previous state.
2
In this mode, the reversing valve is inactive, the temp. setting range is from 16~30
o
C.
3 Protect
function
a. Anti-freezing
function.
i. If compressor have run 6 minutes , and detect T eva < 0
o
C for continuous 3 min-
utes, then the compressor, outdoor fan stopped , indoor fan run at the set fan
speed. After 3 minutes later, it will run at the original state if T eva > or = 10
o
C.
b. Compressor
protection
i. Compressor’s starting interval should be more than 3 minutes no matter in what-
ever modes and conditions. If it’s plugged in first time, the compressor does not
have 3 minutes delay. When compressor is started, it will not stop within 5 min-
utes unless it is plugged out.
c. Overload
protection
i. If it detect the system current surpass the designed 13 A for continuous 3 min-
utes, the machine go into fan mode, when 3 minutes passed and it detect the
current no more than 13 A, it will back to original state. If it detects overloading
states for 6 consecutive times, the machine stops, and must be restarted by re-
mote controller.
Dehumidifying mode
1
The working conditions and control measures
a. If T in > T set + 2
o
C, it is in cooling running, the indoor motor speed can be selected,
and outdoor motor run at low speed.
Model No: AC-S13CGx2.doc
Version 1.0
Summary of Contents for AC-S13CG series
Page 2: ...2 Model No AC S13CGx2 doc 3 Model AC S13CG x 2 Version 1 0 ...
Page 6: ...6 Model No AC S13CGx2 doc Version 1 0 ...
Page 7: ...7 Model No AC S13CGx2 doc Version 1 0 ...
Page 8: ...8 Model No AC S13CGx2 doc Version 1 0 ...
Page 9: ...9 Model No AC S13CGx2 doc Version 1 0 ...
Page 10: ...10 OUTLINES AND DIMENSIONS OF INDOOR UNIT Model No AC S13CGx2 doc Version 1 0 ...
Page 12: ...12 Model No AC S13CGx2 doc Version 1 0 ...
Page 14: ...14 PARTS LIST OF OUTDOOR UNIT Model No AC S13CGx2 doc Version 1 0 ...
Page 21: ......