AJAX ocBridge Plus Manual Download Page 5

PICTURE 24. Service output S properties menu

PICTURE 22. Service outputs setting menu on page “Radio zones”

PICTURE 23. Service outputs’ properties menu Т, B, J

PICTURE 25. Firmware file selection 

When bistable mode is chosen for reaction, service zone reacts by closing/

opening the output depending on “Initial state” setting (NC/NO) until the 

zones returns to the initial state. When the initial state is changed, green 

light “12” of the appropriate service zone (PICTURE 1) turns on. 

Output B – “Battery”. When the sensor the battery has run down, the 

sensor sends the signal about it. When the battery has run down, zone “B” 

does not function for a keyfob SpaceControl, but the message about the 

battery running down can be found in service events log. On the keyfob, the 

discharged battery is shown by its light indication.   

Output J – “Jamming: in case it is found that the radio signal is being jammed, 

the receiver changes the output J condition. Indicator corresponding to 

the output J begins to light depending on the zone settings: the light is 

permanently on if the zone was defined as a bistable one; it turns on for 

the number of seconds specified (1-254 seconds) if the zone was defined 

as an impulse one.    

6.7. Output Т1 is responsible for the ocBridge’s tampers’ state. When the 

receiver is installed in the box, tamper buttons are pressed, the output is 

permanently closed. When at least one tamper unpressed, the output is 

opening and the guard zone sends an alarm signal. It remains in alarm 

state until both tamper buttons are in normal state again and the output 

is closed.

7. FIRMWARE UPGRADE 

7.1. It is possible to upgrade ocBridge’s firmware. Download latest version 

of software from 

www.ajax.systems.

7.2. Firmware is upgraded with a help of configuration software. If the 

ocBridge is connected to configuration software, you should press 

“Disconnect” button without disconnecting the ocBridge itself from PC. 

Then, in the menu “Connection”, you should select a COM port where 

ocBridge is connected. Then, it is necessary to select “Firmware upgrade” 

in drop-down menu and then, pressing the button “Select file”, to show the 

file path to *.aff file with new firmware (PICTURE 25).

Then, it is necessary to power the receiver off with switch “10” (PICTURE 

1) and turn the device on again. After switching on, the upgrade process 

begins automatically. In case the process was accomplished successfully, 

there is a message “Software upgrade is accomplished” and the receiver 

is ready for work.  

 7.3. If there is no message “Software upgrade is accomplished” or there 

were any failures during the software upgrade, you should upgrade the 

software again.

8. CONFIGURATION TRANSFER

It is possible to use the sensors’ configuration transfer to the other device 

ocBridge without having to register the sensors again. For the transfer, it 

is necessary to save the current configuration from “File” menu with “Save 

configuration to file” button (PICTURE 8). Then, it is necessary to disconnect 

the previous receiver and to connect a new one to the configurator. Then, 

it is necessary to upload there a configuration saved on the computer 

using the button “Open the existing configuration” and then to press the 

button “Write down”. After this, the window of sensors’ search will appear 

(PICTURE 26) on ocBridge and the green light indicator will blink for 10 

minutes.

Arm/disarm zone can be set to initial state NC or NO. When the keyfob 

is registered, in arm/disarm zone two buttons are added simultaneously: 

button 1 – arming and button 3 – disarm. To arm, the zone reacts with 

closing/opening the output, depending on the setting “Initial state” (NC/

NO). When this zone is activated, the red light corresponding to it turns on, 

and when it is deactivated, the light “3” (PICTURE 1) is off. 

The activation/

deactivation zone is set by default as trigger.

6.5. The input “IN” is designated for connecting transistor output or the 

central unit (panel) relay (PICTURE 1). If the “IN” input condition changes 

(Closing/Opening), the whole set of sensors connected to the receiver 

are set to “passive” mode (except for the sensors ticked as 24 h active), 

with the initial state restore – the sensors are set to “active”, and the red 

light is on. In case several groups of sensors are used independently on 

the central unit, the ocBridge is to be set to the “active” mode even if 

only one group of central unit is in armed mode. Only when all groups on 

central unit are deactivated, is possible to set the ocBridge and sensors to 

“passive”. Use of “passive” mode of the sensors when system disarmed 

will significantly improve battery life of the sensors.

6.6. 4 outputs (T, S, B, J) correspond to service zones (PICTURE 17). Service 

zones are used for sending operation data to the central unit. Service 

outputs’ functioning is adjustable (PICTURE 23), they can be impulse of 

bistable ones. It is possible to switch off service outputs, in case they are 

not used in security system’s central unit (panel). To switch off untick the 

checkbox against an appropriate output’s name in configuration software 

(PICTURE 22).

If the Impulse mode is selected for reaction, the zone reacts to all activations 

by closing/opening the output depending on “Initial state” setting (NC/NO) 

for the time set in “Impulse time” option (PICTURE 23). By default, the 

impulse time is 1 second and the maximal value is 254 seconds.

  ATTENTION! 

While connecting the keyfob to the wireless sensors’ receiver ocBridge, 

be careful in connecting the keyfob to the zones! Please, don’t connect 

the keyfob to the zones with bistable sensors.

Do not forget: the longer the polling period (PICTURE 22) of the sensors 

is (it varies from 12 to 300 seconds, 36 seconds set by default), the longer 

is wireless sensors’ battery life! At the same time it is suggested not 

to use a long polling period in secure systems for places where delay 

can be critical (for example, in financial institutions). When the polling 

period is too long, the time span of statuses sending from the sensors is 

increasing, which influences secure system’s reaction to service events 

(e.g. lost connection event). The system always reacts immediately to 

alarm events with any polling period.

Output T – “Tamper”: if one of the sensors is opened or separated from the 

assembling surface, its tamper button is activated and the sensor sends 

the alarm signal of opening/breaking.    

Output S – “Lost connection”: if one of the sensors does not send the status 

signal during check time, the sensor changes the output condition S. 

Service zone S will activate after the period of time equal to the parameter 

“Polling period” multiplied by the parameter “Passes number” (PICTURE 

24). By default, if ocBridge does not receive 40 heatbeats from sensor 

successfully, it generates an “Lost connection” alarm.

Reviews: