Technical Data Sheet: FireProtect 2 Jeweller
Easy to install and configure
SmartBracket mounting panel with the ability to align the detector after installation
Remote control and configuring via Ajax apps
Pairing with the Ajax hub via QR code.
Operating principle
Smoke detection
FireProtect 2 detects smoke and does not react
to water vapour thanks to a bispectral optical
sensor with blue and infrared LEDs. LEDs emit
light with different wavelengths, which allows
the detector to determine the size of the volatile
particles and react only to smoke.
The detector's smoke chamber is protected from dust, dirt, and insects. Even if dust enters and settles in the
smoke chamber, it does not threaten or impair the detection. The optical system is designed so that non-
volatile particles or insects cannot be in two beams simultaneously and cause a false alarm.
Detection of a rapid
temperature rise
Two built-in thermistors are responsible for the reaction
to temperature rise. Thermistors are located outside the
detector for faster threat detection.
If the room temperature exceeds 64°C or increases at more than 10°C per minute, the detector recognizes
this as a rapid temperature rise and raises the alarm. The temperature alarm can trigger even if there is no
smoke in the room.