CONFIGURATION DIP SWITCHES S1-1 & S1-2
Open-Loop -- Fan filter unit is controlled by a controller, i.e. on-board potentiometer or
network controller.
Closed-Loop -- A sensor is used to maintain airflow, i.e. room pressure, roomtemp, or a
particle counter.
Analog Setpoint -- Unit is controlled with an analog contoller, i.e. on-board potentiometer or individual wall mounted
controller (must be determined before ordering)
Network Setpoint -- Unit is controlled with a networked controller, i.e. ACC1 or ACM7052 touchscreen controller
*Leave shunt out if using
a 0-20mA or 4-20mA sensor.
SENSOR SHUNT TABLES
Shunt Table for JP1 wiring block
Shunt Table for JP2 wiring block
NOTES:
- JP1 is for signal input
- JP2 is for output power
- connect COM/5V --> 5V power supplied
- connect COM/VSEL with 10V shunt -->
10V power supplied
- connect COM/VSEL with V.RFU shunt -->
Full wave rectified power supplied
(~33VDC)
- INP1 on JP1 wiring block is for monitoring only
- 0 - 10VDC
- 0 - 5VDC
- 0 - 20mA
- 4 - 20mA
- INP2 on JP1 wiring block is for closed-loop
feedbackor monitoring
- Controling airflow by room pressure
or particle counter
Switch
S1-1
S1-2
Control Loop Mode Setpoint Source
OFF
Open-Loop Control Analog Setpoint
ON
Closed-Loop Control Network Setpoint
Shunt
JP420
JFBS
JVS-1*
JVS-2*
OUT
0 - 20mA
ANALOG
0 - 5VDC
0 - 5VDC
IN
4 - 20mA
N/A
0 - 10VDC
0 - 10VDC
Center Pin to...
JPUD1:INP1
JPUD2:INP2
No connection
ANALOG 5V or 10V
ANALOG 5V or 10V
20mA
ANALOG 20mA
ANALOG 20mA
+5V PU
DIGITAL 10kΩ pull-up TO 5V DIGITAL 10kΩ pull-up TO 5V
Center Pin to...
JVDC
No Connection
VSEL = no connection; open
10V
VSEL = 10V regulated
V.RFU
VSEL = DC filtered, unregulated, ~33VDC
DRAWING NAME
DRAWN
CATEGORY
CHKD
APRVD
PRODUCT
SIZE
TAG
QTY
BRS/SLG
06/13/22
CRITI-CLEAN ULTRA INSTALLATION MANUAL
SSLFHFD-FFU-RF-MEA
REV # F
SHT 18 27
/
SCL
DO NOT
SCALE
1:10
STAINLESS STEEL
CRITI-CLEAN ULTRA
REVERSE FLOW - FAN FILTER UNITS