STAINLESS STEEL
SSLFHFD-FFU
CRITI-CLEAN ULTRA FAN FILTER UNIT
NETWORKING
When networking the fan filter units either in a local area network (LAN) or connecting to
a BAS/BMS system, each unit is connected in a "straight-through" daisy-chain using Cat5e or
Cat6 network cables and the on-board RJ45 connectors.
If field cutting network cables, it is important for each end of the cable to be wired identically.
However, assembled network cable are available; field assembled cables are the leading
cause of problems in new systems.
ACC1001 control used
as an example. Other
controller options
available.
Power supply board
can be located in the
lead FFU or in the controls
enclosure.
INSTALL AND OPERATION
DRAWING NAME
DRAWN
MATERIAL
CHKD
APRVD
FINISH
SIZE
ENGINEER
CONTRACTOR
TAG
QTY
BRS
REV # E
SHT 18 30
/
SCL
DO NOT
SCALE
1:10
JOB NAME