Activation delay.
It allows to set a delay time in the power on of the production unit, configurable in minutes, from 0
to 7. (Default preset to 3 minuts).
•
LWT temperatures.
(Only available in installations with gateway AZX6GAW[XXX] provided that the aerothermal unit is
not configured to work automatically, allowing the imposition of working temperatures).
It allows to set the LWT
temperaturas for the heatting and cooling modes of the aerothermal unit. Selectable values depends on each
particular aerothermal unit. Default presets are:
-
Air in cooling mode: 10 ˚C
-
Radiant in cooling mode: 18 ˚C
-
Air in heating mode: 50 ˚C
-
Radiant in heating mode: 35 ˚C
•
DHW function.
(Only available in installations with AZX6GAW XXX control gateways)
It allows to turn on/off the Domestic
Heat Water (DHW) function in the systems connected to the CCP. Activated by default.
•
Cooling mixing valve
(only available in installations with aerothermal gateway). It allows you to configure the
operation of your installation depending on whether or not you have a cooling mixing valve.
Select Manual in the case of having cooling mixing valves in your installation, in which case they must be set at 18°C.
If the installation does not have a cooling mixing valve, select Auto so that the installation works automatically with
the temperature read by the system. By default it is set as Manual.
SELF-DIAGNOSE
Airzone production control boards have LEDS integrated in order to detect malfunctions.
Meaning
D1
Receiving data from domotic bus
Blinking
Green
D2
Transmitting data from domotic bus
Blinking
Red
D3
Microproccesor performance
Blinking
Green
D11
Power supply
Solid
Red
D22…D27
Leds of relay state
Switches
Green
D68
Data transmission from integration bus
Blinking
Red
D69
Data reception from integration bus
Blinking
Green