Error 13: Main Board and AZRA6CM1VALC module communication error
This incident blocks the control of the zone. To solve this incident check:
1.
Status of the control module of the radiant elements: Correctly powered.
2.
Status of the control module of the radiant elements and the main control board: Airzone connection bus LEDs are
operating properly.
3.
Connection: Check the polarity of the connectors of the main control board and the radiant element board.
4.
Wiring: Disconnect the terminal from the Airzone connection bus and check that the voltage between the poles (A/-)
and (B/-) is about 1 Vdc.
Error 17: Airzone-Lutron integration Gateway-System
The system loses communication with the Gateway. Check the gateway is properly plugged to the production control board
as well as the connection between the production control board AZX6CCP and the system main board.