THERMOSTAT AND MANUAL RESET
The model water heaters listed above are equipped with a high temperature limit
as a cut-off device. Temperature above 82
°
C will cause manual reset button to trip
shutting down the electric element.
To activate element, the water temperature must be below 37
°
C. Push reset
button to
ANODE PROTECTION
The tank in this water heater is protected by a magnesium or aluminum anode to
prolong the life of the tank. Removal of the anode will decrease tank life and will
void the warranty on the inner tank. Anode must be checked every 6 (six) months,
and replaced if below 50% of original diameter, failure to do so will void your
warranty. Use only genuine Suburban anode rods. Use of other anodes may void
the warranty. Anode performance depends on water quality, therefore are
NOT
covered by warranty.
To prevent a water leak when replacing the anode rod, a pipe thread sealant
approved for potable water (such as Teflon Tape) must be applied to the threads
of the anode rod. Proper application of a thread sealant will not interfere with the
anode’s tank protection.
Anode Dimensions: Length - 215mm, Diameter - 17mm.
NOTE
: Tank is drained by removing anode rod (See “Drain and Storage”
instructions).
To extend anode life, drain water from tank whenever RV is not being used. Avoid
any extended time of non-use with water in tank.
Also, refer to the section on winterizing.
WARNING! Do not replace the anode rod with any non-Suburban
accessory part, such as an “add-on” electric heating element. Items such
as these are not approved to be installed in Suburban products. They
could create an unsafe condition and will also void all warranties.
PRESSURE RELIEF VALVE
The temperature and pressure relief valve is designed to open if the temperature
of the water within the heater reaches 98.9 degrees Celsius, or if the water
pressure in the heater reaches 850 kPa. Recreational vehicle water systems are
closed systems and during the water heating cycle the pressure build-up in the
water system will reach 850 kPa. When this pressure is reached, the pressure
relief valve will open and water will drip from the valve. This dripping will continue
until the pressure is reduced to below 850 kPa. Once the pressure has dropped
below 850 kPa, the valve will close. This condition is normal and does not indicate
a defective relief valve.
WARNING! Do not plug, cap or reduce the outlet pressure and temperature
valve.
The pressure-relief device is to be operated regularly to remove lime deposits and
to verify that it is not blocked.
DANGER! Failure to operate the relief valve easing gear at least once every
six months ma
y result in the water heater exploding. Continuous leakage of
water from the valve may indicate a problem with the water heater.
WATER WEEPING OR DRIPPING
FROM PRESSURE RELIEF VALVE
You may experience water weeping or dripping from your water heater’s Pressure
and Temperature (P & T) Relief Valve when your water heater is operating. Water
weeping or dripping from the P & T Valve does not always mean the P & T Valve
is defective. As water is heated, it expands. The water system in a recreational
vehicle is a closed system and does not allow for the expansion of heated water.
When the pressure of the water system exceeds the relieving point of the P & T
Valve, the valve will relieve the excess pressure. Suburban recommends that a
check valve not be installed directly at the inlet to the water heater tank. This will
increase weeping of the pressure relief valve.
One way to reduce the frequency of this occurrence is to maintain an air pocket
at the top of the water heater tank. This air pocket will form in the tank by design.
However, it will be reduced over time by the everyday use of your water heater.
To replenish this air pocket:
1.
Turn off water heater.
2.
Turn off cold water supply line.
3.
Open a tap in the RV.
4.
Pull out on the handle of the Pressure Relief (P & T) Valve and allow water
to flow from the valve until it stops.
5.
Release handle on P & T Valve - it should snap closed.
6.
Close tap and turn on cold water supply; as the tank fills, the air pocket will
develop.
Repeat this procedure as often as needed to reduce the frequency of the weeping
of the P & T Valve. If the weeping persists after following this procedure, you may
elect to install an expansion or accumulator tank in the cold water line to relieve
the pressure caused by thermal expansion.
Suitable fittings are required to be installed in the pressure relief valve for piping
water away. A hole for the discharge pipe must be drilled in the bottom of the
control housing and the piping passed through the hole. The hole through which
the piping passes must be sealed water tight.
The discharge pipe must not be reduced in size along its length. The length and
number of bends should be kept to a minimum and should be supported in a
manner to reduce the risk of crushing or blockage.
Please contact your local dealer for assistance.
DRAINING AND STORAGE INSTRUCTIONS
If unit is to be stored during the winter months, the heater must be drained to
prevent damage in the case of freezing temperatures.
1.
Turn off electrical supply to the water heater.
2.
Turn off pressure pump on the water system.
3.
Open both hot and cold water taps.
4.
Open the drain on the water heater. (Remove anode rod)
5.
Follow RV manufacturer’s instructions for draining of the entire water
system.
NOTE
: Be certain to refill water heater with water before using the appliance.
240 V.A.C. ONLY
DISCONNECT POWER SUPPLY BEFORE REMOVING COVER
SUBURBAN MANUFACTURING COMPANY; DAYTON, TENNESSEE
240 V.A.C. - SINGLE PHASE - 1440 WATT ELEMENT - 50 CYCLE
TOTAL CONNECTED WATTS = 1440 - AMPS = 6
CODE
BLACK
BK
COLOR
W
WHITE
HI-
LIMIT
T'STAT
BK
BK
ELECTRIC
ELEMENT
BK
GROUNDING SCREW
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE HEATER MUST
BE REPLACED, IT MUST BE REPLACED WITH 14GA. 105°C WIRE OR ITS
SWITCH
BK
G
G
GREEN
W
A
N
MAX. WORKING PRESSURE 850 KPA
EQUIVALENT. INDOOR USE ONLY APP. NO. Q00145
Figure 5
RESET BUTTON
240 V.A.C. T-STAT
HI-LIMIT
Figure 6
ANODE ROD
Figure 7
4