Testing the Thermostat

Note: The LL357D4 does not require the units to be in phase.
Procedure: (A/C Testing with LL357D4 Lead/Lag Control for Two Units)
UP
 - Used to increase the time, set temperatures and to adjust 
configuration settings.

DOWN - Used to decrease the time, set temperatures and to 
adjust configuration settings.

SYS (left) - Used to change from OFF, HEAT, COOL and AUTO changeover modes.

RIGHT - Used to turn on and off the indoor fan.

UP, SYS and RIGHT - Held in simultaneously for 10 seconds to lock and unlock the thermostat.

DOWN and SYS - Pressed simultaneously to display outdoor temperature if outdoor remote sensor is 
connected.

1.  Set the cooling temperature on the wall thermostat to a point higher than the  ambient temperature. 

Set the heating temperature to a temperature that is lower than the ambient temperature. Turn the 
selector switch to the “off” position. 

2.  Set the time delay on unit No. 1 to “3” minutes, and No. 2 to “5” minutes.
3.  Set the change over setting of the enthalpy control to the “d” setting (ComPac® II A/C only).
4.  Provide power to A/C units and turn disconnects on.
5.  Check incoming power to each unit. For units designed for operation on 208/230v, 60hz power 

supply, the transformer is factory wired for a 230 power supply. For a 208 power supply remove the 
orange lead from the transformer and connect the red lead. Insulate the orange lead.

6.  Cooling. Use the SYS switch to set the thermostat to “AUTO”. Slowly lower the cooling temperature 

until the switch closes. The indoor fan should operate on the lead unit. Once the indoor fan turns 
on, allow approximately 3 to 5 minutes for the compressor to start. Note that the outdoor fan may 
not come on immediately because it is cycled by refrigerant pressures. Next, lower the temperature  
until the switch closes. Follow the above procedures for the lag unit.

 

The green light on the lead lag control should be on. One amber light will be on to identify the lead 
unit. The other light should be off. If the lag unit comes on with the lead unit the light for the lag 
unit will not come on. You should never have all 3 lights on at one time.

 

Allow the units to run for 2 to 3 minutes then check the temperature differential between the return 
air and the supply air with digital thermometer. The temperature differential should be between 12 
and 20 degrees depending on ambient temperature.

 

Next, slowly raise the cooling temperature  until the switch opens. The compressor and outdoor fan 
should turn off. The indoor fan will continue to run for “90” seconds until the fan purge times out. 
Raise the temperature until the switch opens. The lead unit will shut down accordingly to the same 
procedures as outlines above.

 

Note: (ComPac® II A/C only) To check the system operation under different ambient conditions, 
the air temperature and enthalpy sensors must be “tricked”. When outdoor ambient conditions 
are higher than the control setting, a component cooler aerosol may be sprayed directly into the 
enthalpy sensor to stimulate low enthalpy conditions, causing the economizer damper to open.

 

Alternately, when outdoor conditions are lower than the set point, a source of heat such as a hair 
dryer can be directed on the enthalpy sensor to simulate warm conditions, which will bring on 
mechanical cooling and start the compressor.

7. Heating. Slowly raise the heating temperature until the switch closes. The fan and electrical heat 

should immediately cycle on. The unit should start blowing warm air in 2 to 3 minutes. Next, raise 
the temperature until the switch closes. Follow the above procedures for lag unit.

 

Hold the manual advance button in for nine seconds the lead lag lights should switch. Next, slowly 
lower the temperature until the switches open. The  lag unit should shut down immediately. Next, 
slowly lower the temperature until the switch opens, the lead unit should shut down immediately.

8. Replace thermostat cover and panels on the unit.

Summary of Contents for Marvair LL357D4

Page 1: ...ng power outages no batteries required Programming not required Digital display shows temperature in F or C Room Temperature Offset Used to calibrate displayed room temperature with actual room temper...

Page 2: ...box for control wiring to air conditioners Low Voltage Wiring 1 All wiring must comply with local codes and ordinances 2 Disconnect power to prevent electrical shock or equipment damage 3 On dual uni...

Page 3: ...lectrical codes and ordinances Note Mount the thermostat about five feet above the floor Do not mount the thermostat on an outside wall in direct sunlight behind a door or in an area affected by a ven...

Page 4: ...stem The LL357D4 functions with air conditioners with electric heat systems To configure the LL357D4 perform the following steps 1 Verify that the LL357D4 is in the OFF mode Press the SYS left button...

Page 5: ...t up for Non Heat Pump and Type of Heat Electric Press the Up or Down button to select scale Press the Right button to advance to the next screen Press the Up or Down button to select Press the Right...

Page 6: ...set to 0 will display Press the Up or Down button to select Press the Right button to advance to the next screen 12 Temperature Sensor 1 3 1 Only on board sensor determines room temperature 2 Only re...

Page 7: ...n the lead lag control should be on One amber light will be on to identify the lead unit The other light should be off If the lag unit comes on with the lead unit the light for the lag unit will not c...

Page 8: ...ode In this mode the thermostat controls the heating system When the heat is on the flame icon appears on the display Cool Mode In this mode the thermostat controls the cooling system When the the uni...

Page 9: ...de steps 2 3 Status indicator light does not come on during call for Cooling or Heating Turn status indicator light function on See Config Mode Step 14 Room temperature is not correct Calibrate thermo...

Page 10: ...of compressors Select non heat pump and Electric 1 GAS 7 Auxiliary Delay On Set the time delay in minutes for aux heat to be locked out after a call for second stage Set to 0 minutes 1 0 00 8 Lockout...

Page 11: ...LL357D4 PDS 4 2011 11 Notes...

Page 12: ...e at www marvair com for the latest product literature Detailed dimensional data is available upon request A complete warranty statement can be found in each product s Installation Operation Manual on...

Reviews: