Airxcel 9630-352 Installation, Operation & Application Manual Download Page 2

Conditions of Heat Pump Lockout (Set Point 70°F)

Operation Chart

The chart below shows the system functions. After the entire air conditioning and heating 
system is installed, check each position function.

*There is a 3 minute anti-short cycle delay timer built into the thermostat.

Mode

Call

Operation

Fan Low

No

GL-Fan Low (Gray) energized

Fan Hi

No

GH-Fan High (Green) energized

Cool On 

High

No

GH-Fan High (Green) energized

Cool On 

High

Yes

GH-Fan High (Green) energized, Y-Compressor (Yellow) energized

Cool On 

Low

No

GL-Fan Low (Gray) energized

Cool On 

Low

Yes

GL-Fan Low (Gray), Y-Compressor (Yellow) energized

Cool Auto 

Low

No

No function occurs

Cool Auto 

Low

Yes 

GL-Fan Low (Gray) energized, Y-Compressor (Yellow) energized

Cool Auto 

High

No

No function occurs

Cool Auto 

High

Yes

GH-Fan High (Green), Y-Compressor (Yellow) energized

Heat Gas

No

No function occurs

Heat Gas

Yes

W-Furnace (White)  energized

Electric 

Heat

No

No functions occur in this mode

Electric 

Heat

Yes

WHP - Heat Pump (White/Black) will be energized

Electric 

Heat 

Backup

Yes (5° 

Below 

Setpoint)

WHP - Heat Pump (White/Black) and WF-Furnace (White) will be 
energized 

Indoor

Temp (°F)

Operation 
of Unit

70+

No operation.

69

Heat pump turns on as primary heat source.

71

Heat pump turns off, thermostat is satisfied.

69

Heat pump turns on as primary heat source.

65

Gas heat turns on at 5 degrees from first stage (heat pump cannot satisfy 
demand).     

First Strike on backup counter.

71

Gas heat and heat pump turn off, thermostat is satisfied.

69

Heat pump turns on.

65

Gas heat turns on at 5 degrees below first stage (heat pump cannot satisfy 
demand).     

Second Strike on backup counter.

71

Gas heat and heat pump turn off, thermostat is satisfied.

69

Heat pump turns on.

65

Gas heat turns on at 5 degrees from first stage (heat pump cannot satisfy 
demand). 

   Third Strike on backup counter. Heat pump is locked out for 1 hr. 45 min.

Backup counter reset if heat pump runs for 20 minutes with no call for back up heat.

71

Gas furnace turns off, thermostat is satisfied.

69

Gas furnace turns on, primary heat source during lockout. 

71

Gas furnace turns off, thermostat is satisfied.

1 hour 45 minute lockout ends.

69

Heat pump turns on and is restored to the primary heat source.

65

Gas furnace turns on and becomes the primary heat source. Heat pump 
turns off for another 1 hour and 45 minutes.

71

Gas furnace turns off, thermostat is satisfied.

1 hour 45 minute lockout ends.

69

Heat pump turns on and resumes primary heat source function.

71

Heat pump turns off, thermostat is satisfied.

Conditions and example for resetting the backup counter

69

Heat pump turns on.

65

Gas heat turns on at 5 degrees from first stage (heat pump cannot satisfy 
demand).

   First Strike on backup counter.

71

Gas heat and heat pump turn off, thermostat is satisfied.

69

Heat pump turns on.

65

Gas heat turns on at 5 degrees from first stage (heat pump cannot satisfy 
demand).

   Second Strike on backup counter

71

Gas heat and heat pump turn off, thermostat is satisfied.

69

Heat pump turns on and runs for 20 minutes without a call for backup heat. 

71

Heat pump turns off, thermostat is satisfied (backup counter reset).

69

Heat pump turns on.

65

Gas heat turns on at 5 degrees from first stage (heat pump cannot satisfy 
demand).

   First strike on backup counter

Backup timer will reset anytime the Heat Pump operates for more than 20 minutes 

and satisfies the thermostat without calling for backup heat.

ZONE NAME:  Assigns a name or 

description to the 
thermostat (maximum of 7 
characters).

THERMOSTAT ID: Displays thermostat’s 

6 digit ID

FUNCTIONS: Displays available modes.
SET: Saves assigned zone name/

description.

CANCEL: Reverts to main screen.
REMOVE THERMOSTAT: Removes 
thermostat from the 

RV Climate app.

Controlling the  

thermostat via RV  

Climate app

1.  Slide screen to the left (2nd screen).
2.  Tap the icon displaying the current  

settings [

Kitchen 75 FAN HIGH].

3.  Select the desired temperature/mode.
4.  Press “

SET”.

Removing a previously paired thermostat

1.  Using the 

RV Climate app, slide screen to the left (2nd screen). 

2.  Press 

.

3.  On the following  page select “

REMOVE THERMOSTAT” and press “OK”.

 Details (2nd Screen)

RV Products

A Division of Airxcel, Inc., P.O. Box 4020, Wichita, KS 67204

www.Airxcel.com

LIAF253

This device complies with part 15 of the FCC Rules. Operation 
is subject to the following two conditions: (1) This device may 
not cause harmful interference, and (2) this device must accept 
any interference received, including interference that may cause 
undesired operation.

NOTE: 

This equipment has been tested and found to comply with the limits 

for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection against harmful interference 
when the equipment is operated in a commercial environment. This equipment 
generates, uses, and can radiate radio frequency energy and, if not installed 
and used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in a 
residential area is likely to cause harmful interference in which case the user 
will be required to correct the interference at his own expense.