background image

26

SERVICING

Routine servicing
- To ensure the correct operation of the ins-

tallation, it is necessary to have preventive
maintenance of the indoor and outdoor units
carried out by qualified personnel.

General installation
- Carry out a visual inspection of the complete

installation in service.

- Check the general cleanness of the instal-

lation, and check that the condensate
evacuations are not blocked, particularly on
the indoor unit, before the summer season.

- Check the condition of the tray.

OUTDOOR UNIT

Coolant system
- Clean the heat exchanger using a special

product for aluminium-copper heat
exchangers, and rinse with water. Do not use
hot water or steam, as this could cause the
pressure of the coolant to increase.

- Check that the surface of the aluminium fins

of the heat exchanger is not damaged by
impacts or scratches, and clean with an
appropriate tool if necessary.

Electrical section
- Check that the main power supply cable is

not damaged or altered in such a way as to
affect the insulation

- Check that the interconnecting cables

between the two units are not damaged or
altered, and that they are correctly
connected.

- Check the earth connection.

INDOOR UNIT

- In order for the installation to operate

correctly, it is essential to regularly clean the
air filter located in the intake of the indoor
unit.

- When clogged, the filter reduces the air flow

through the heat exchanger of the indoor
unit, which in turn reduces the efficiency of
the installation and inhibits the cooling of the
fan motor.

- Check the cleanness of the indoor heat

exchanger.

CAUTION

BEFORE CARRYING OUT ANY OPERA-

TION ON THE EQUIPMENT, CHECK

THAT THE ELECTRICAL POWER

SUPPLY IS SWITCHED OFF AND THAT

IT CANNOT BE SWITCHED ON

INADVERTENTLY.

SX

 

Split system for wall / ceiling mounting

MANUAL MENU

Summary of Contents for SX 12 RCC

Page 1: ...LATION INSTRUCTION TH 3990012 06 Read this instruction sheet carefully before installing retain it safely for future reference SX 16 RCC 18 RCC 24 RCC 30 RCC Read this instruction sheet carefully befo...

Page 2: ...SX Split system for wall ceiling mounting MANUAL MENU...

Page 3: ...with the same circuit WARNING Cutoff power supply before starting to work on the appliance The manufacturer declines any responsibility and the warranty becomes void if these instructions are not res...

Page 4: ...te distance between mounting holes 1 sensor connecting cable 1 active charcoal filter and its support SUMMARY DESCRIPTION Dimensions of Indoor Units 4 Dimensions of Outdoor Units 5 INSTALLATION Locati...

Page 5: ...5 630 A MODEL 12 16 18 A 820mm MODEL 24 30 A 1200mm DIMENSIONS OF INDOOR UNIT SX Split system for wall ceiling mounting MANUAL MENU...

Page 6: ...BE FLARED LIQUID TUBE FLARED VALVE CONNECTIONS AIR INTAKE AIR OUTLET 237 50 100 MIN WALL MINIMUM CLEARANCE 800 MIN WALL WALL 100 400 MIN WALL 500 MIN FROM TOP 760 544 472 58 48 15 300 325 370 WIRING C...

Page 7: ...ort of the SX using the installation template supplied with the unit The cut outs for the unit are shown on this template Reminder of MINIMUM clearances to be provided Coolant connections can be made...

Page 8: ...r determining the outlet for the condensate evacuation LH RH rear make sure that the wall mounting is installed with a slope which favours this evacuation Secure the wall support with 4 screws not sup...

Page 9: ...ON OF THE OUTDOOR UNIT Minimum clearance to respect in mm Almohadillas de montaje x 4 Wall bracket not supplied CAUTION If the heat pump outdoor unit is installed in an area where the outdoor temperat...

Page 10: ...Insulation sleeve The indoor unit may be installed above or below the unit The flare couplings are available as accessories in standard lengths of 2 5 5 and 8 m The pipes are delivered coiled and equ...

Page 11: ...tubing on the wall support before installing the unit using the template supplied Place the tube locating template on the wall support INSTALLATION OF TUBING ON WALL SUPPORT After choosing your coola...

Page 12: ...lamps provided Remove the tubing template you can now install your unit on its support NOTE output to the rear The slanted hole prevents condensates or rain from entering the unit Fit a Dia 70 mm slee...

Page 13: ...RH side panels Screws FOR THE INTAKE GRID 1 Pull the grid forwards 2 Remove the two end screws 3 Unscrew the central screw but do not remove it completely 4 Unhook the grid FORTHESIDEPANELS 5 Remove...

Page 14: ...the diagram below for installation of the SX Ceiling mounting refer to the NOTE below Wall mounted For ceiling mounting install the two clamp screws provided for the unit on the support Ceiling mounte...

Page 15: ...the case of a connection to the wastewater system 2 5 cm m slope An S bend must be installed on the evacuation duct below the level of the recovery tray of the unit Provide insulation for the evacuati...

Page 16: ...95 Nm 2 Connect the vacuum pump with the flare coupling of the outdoor unit equipped with a process valve 3 Start the vacuum pump and check that the needle of the indicator goes down to 0 2 mm Hg The...

Page 17: ...4 N 3 V 0 3 2 t i n u e d i s t u o n i e g r a h C d e g r a h c y r o t c a f m 4 r o f C G p m u p t a e H e b o t e g r a h c 2 2 R e t i s e h t n o d e d d a l e d o m p m u p t a e H COOLING SP...

Page 18: ...5 m 1 2 s r g 5 5 2 s r g 0 6 5 m 2 2 s r g 0 7 2 s r g 0 0 6 m 3 2 s r g 5 8 2 s r g 0 4 6 m 4 2 s r g 0 0 3 s r g 0 8 6 m 5 2 s r g 5 1 3 s r g 0 2 7 LENGTH OF CONNECTIONS TABLE B R22 charge depende...

Page 19: ...or and connect the sensor wire supplied To configure for COOLING ONLY Remove the RC marked MODEL PLUG and replace with ST marked MODEL PLUG mounted on the electronic circuit board MODEL PLUG SX Split...

Page 20: ...e AAA LR 03 AMG SET CLR HOUR CONFIGURATION OF REMOTE CONTROL To change the configuration 1 Remove the batteries 2 Set the switches 3 MANDATORILY perform a RESET see below 4 Reinstall the batteries RES...

Page 21: ...C G X S s e p i p g n i k n i L n o i t c e s e l b a C 3 x 1 5 4 x 1 5 5 2 7 6 8 10 3 x 1 5 4 x 1 5 8 5 12 12 16 3 x 2 5 4 x 1 5 11 9 16 16 16 3 x 2 5 5 x 1 5 16 2 23 5 25 25 3 x 2 5 5 x 1 5 SX12 SX1...

Page 22: ...SUPPLY TO INDOOR UNIT POWER SUPPLY TO OUTDOOR UNIT WITHOUT ELECTRIC HEATING SX12 16 230V WITHOUT ELECTRIC HEATING 230V 50Hz SX18 24 ELECTRICAL CONNECTIONS SX Split system for wall ceiling mounting MAN...

Page 23: ...WITHOUT ELECTRIC HEATING POWER SUPPLY TO OUTDOOR UNIT SX30 230V 50Hz WITH WITHOUT ELECTRIC HEATING SX18 24 28 30 3N 400V SX Split system for wall ceiling mounting ELECTRICAL CONNECTIONS MANUAL MENU...

Page 24: ...POWER Comes on as soon as the unit is energised E PROGRAMMING Comes on during operation Flashes to indicate that the remote control signal has been received and stored in the memory F FILTER Comes on...

Page 25: ...filter indicator light F goes out Do not operate the air conditioner without the filter Cleaning of the air conditioner Rub the inside of the unit with a soft dry cloth Do not use hot water or volati...

Page 26: ...is not damaged by impacts or scratches and clean with an appropriate tool if necessary Electrical section Check that the main power supply cable is not damaged or altered in such a way as to affect t...

Page 27: ...THE INDOOR LIQUID TUBE DURING INSTALLATION WITHOUT THIS KIT THE UNIT WILL NOT OPERATE PROPERLY IN THE HEATING MODE See BELOW FIGURE 1 2 3 4 Fig 1 LIQUID TUBE 2 SUCTION TUBE 3 RESTRICTOR 4 INDOOR UNIT...

Page 28: ...MANUAL MENU...

Page 29: ...MANUAL MENU...

Page 30: ...MANUAL MENU...

Page 31: ...MANUAL MENU...

Page 32: ...MANUAL MENU...

Page 33: ...fices on the parkSuite 27 8 Greenhill Road Wayville SA 5034 TEL 08 8372 7866 FAX 08 8372 7816 PERTH Suite 23 350 Cambridge St Wembley WA 6014 TEL 08 9284 0800 FAX 08 9284 0600 NEWCASTLE Suite 3 19 Dar...

Reviews: